FIR16-00606
| INSP-Final Inspection | 11/21/2017 | 11/28/2017 | 11/28/2017 3:51:51 PM | P | FAIL |
|
|
1. Room 201 has exposed CPVC in water heater room. Head to close to ceiling fan. 2. Head in corridor between rooms 205 & 207 needs to be changed to an intermidate temperature, head is within 12 inches of heat register. 4. Room 213 has head to low in bathroom, same head is missing escutcheon. 5. Rooms 209, 214, 216, 220, 306, 309, and 504 has escutcheons missing. 8. Rooms 205, 219, 301, 414, 507, 516, and 519 has sprinkler heads to close to ceiling fans. 9. All exposed CPVC needs to be covered by sheetrock.
|
FIR17-00234
| INSP-Final Inspection | 11/28/2017 | 11/28/2017 | 11/28/2017 3:30:23 PM | P | FAIL |
|
|
Fire panel needs to be System is Normal before inspection can be started.
|
FIR17-00501
| INSP-Supply line flush | 11/27/2017 | 11/28/2017 | 11/28/2017 3:28:07 PM | P | CANC |
|
|
Flush rescheduled for 29NOV2017, this request is cancelled.
|
BLD17-04192
| FIRE-Final Inspection | 11/28/2017 | 11/28/2017 | 11/28/2017 11:04:19 AM | P | PASS |
|
|
Previously noted items for life fire safety have been addressed. Final life fire sprinkler inspection passed/complete.
|
FIR17-00601
| INSP-Final Inspection | 11/21/2017 | 11/28/2017 | 11/28/2017 10:07:42 AM | P | CANC |
|
|
Inspection request cancelled per conversation with point of contact, Travis Phone #: ###-####, inspection will be rescheduled for a later date.
|
FIR17-00501
| INSP-Sprinkler Rough-in/Hydro | 11/27/2017 | 11/28/2017 | 11/28/2017 10:05:24 AM | P | CANC |
|
|
Hydrostatic test cancelled per conversation with point of contact, Jim Baker Phone #: ###-#### , hydrostatic test will be rescheduled for a later date.
|
BLD17-03914
| FIRE-Final Inspection | 11/27/2017 | 11/28/2017 | 11/28/2017 9:59:29 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection for area of work passed/complete.
|
BLD17-02553
| FIRE-Final Inspection | 11/27/2017 | 11/28/2017 | 11/28/2017 9:45:07 AM | A | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection for area of work passed/complete.
|