Inspections for the day of: Tuesday, November 28, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00606 INSP-Final Inspection11/21/201711/28/201711/28/2017 3:51:51 PMPFAIL
1. Room 201 has exposed CPVC in water heater room. Head to close to ceiling fan.
2. Head in corridor between rooms 205 & 207 needs to be changed to an intermidate temperature, head is within 12 inches of heat register.
4. Room 213 has head to low in bathroom, same head is missing escutcheon.
5. Rooms 209, 214, 216, 220, 306, 309, and 504 has escutcheons missing.
8. Rooms 205, 219, 301, 414, 507, 516, and 519 has sprinkler heads to close to ceiling fans.
9. All exposed CPVC needs to be covered by sheetrock.
FIR17-00234 INSP-Final Inspection11/28/201711/28/201711/28/2017 3:30:23 PMPFAIL
Fire panel needs to be System is Normal before inspection can be started.
FIR17-00501 INSP-Supply line flush11/27/201711/28/201711/28/2017 3:28:07 PMPCANC
Flush rescheduled for 29NOV2017, this request is cancelled.
BLD17-04192 FIRE-Final Inspection11/28/201711/28/201711/28/2017 11:04:19 AMPPASS
Previously noted items for life fire safety have been addressed. Final life fire sprinkler inspection passed/complete.
FIR17-00601 INSP-Final Inspection11/21/201711/28/201711/28/2017 10:07:42 AMPCANC
Inspection request cancelled per conversation with point of contact, Travis Phone #: ###-####, inspection will be rescheduled for a later date.
FIR17-00501 INSP-Sprinkler Rough-in/Hydro11/27/201711/28/201711/28/2017 10:05:24 AMPCANC
Hydrostatic test cancelled per conversation with point of contact, Jim Baker Phone #: ###-#### , hydrostatic test will be rescheduled for a later date.
BLD17-03914 FIRE-Final Inspection11/27/201711/28/201711/28/2017 9:59:29 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection for area of work passed/complete.
BLD17-02553 FIRE-Final Inspection11/27/201711/28/201711/28/2017 9:45:07 AMAPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguisher is in place with a current inspection tag. Final life fire safety inspection for area of work passed/complete.