Inspections for the day of: Friday, November 29, 1996.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE95-02210 INSP - Permanent service11/29/199611/29/199611/29/1996 12:00:00 AM FAIL
/ / 315 - 1995 street lignting Columbia Village # 17 53 failed cor.and reinspection fee due sent.NEC, 250-94 GED minimum size #8 copper,250-92 provide protection for#8 250-83(c) 110-14(a) jf
ELE96-03908 INSP - Ele Rough-In/Perm Svc11/29/199611/29/199611/29/1996 12:00:00 AM PASS
/ / 315 - 09&53 ok jf 11rms 1a/c 200a u/g new
ELE96-03937 INSP - Permanent service11/27/199611/29/199611/29/1996 12:00:00 AMANR
11/29/96 315 - not ready jf
ELE96-01874 INSP - Final11/27/199611/29/199611/29/1996 12:00:00 AMAPASS
11/29/96 315 - jack/he said he talked to you and that you knew he had it coming back out. therefore i put it in for friday a.m. 14 ok jf
ELE96-03943 INSP - Permanent service11/27/199611/29/199611/29/1996 12:00:00 AMACANC
11/29/96 315 - inspection is for a 09
ELE95-01116 INSP - Conference11/29/199611/29/199611/29/1996 12:00:00 AMPPASS
11/29/96 315 - 01 ok jf
ELE96-02952 INSP - Final11/29/199611/29/199611/29/1996 12:00:00 AMPPASS
11/29/96 315 - 14 ok jf
ELE96-03938 INSP - Final11/29/199611/29/199611/29/1996 12:00:00 AMPPASS
11/29/96 315 - 14 ok jf