Inspections for the day of: Friday, November 29, 2002.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-03719 Temporary Service11/27/200211/29/200211/29/2002 12:00:00 AMAFAIL
###-#### kathy 11/29/2002 12:22:06 PM cor. posted called left message 250.119, 250.64 (B) protect #8 grd, 406.8(B)(1) in use covers, 110.3 (A) ringed wire 110.12 (C) clean foreign material from x former, 110.14(A) tighten all nuts bolts and lugs, 450.11 name plate and marking for x former, 450. 22 xformer shall be wheather proof 11/29/2002 1:50:02 PM
ELE02-03694 Electrical Rough-In11/27/200211/29/200211/29/2002 12:00:00 AMAPASS
###-#### ok 11/29/2002 10:48:41 AM
ELE02-02559 Final11/27/200211/29/200211/29/2002 12:00:00 AMAPASS
dan; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie ok 11/29/2002 11:52:58 AM
ELE02-03457 Electrical Rough-In11/29/200211/29/200211/29/2002 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 11/29/2002 at 11:03:26. Contact: ###-####. electrode ok for cover 11/29/2002 4:29:24 PM
ELE02-02728 Rough-In Permanent Service11/25/200211/29/200211/29/2002 12:00:00 AMPFAIL
GARY ###-#### CELL ###-#### cor. posted met with owner 230.24(A) except #2, 230.2 only 1 p/s allowed, 250.53 (B) grd rods 6ft apart, 250.52(A)(1) or 104 11/29/2002 4:03:33 PM
ELE02-03580 Rough-In Permanent Service11/27/200211/29/200211/29/2002 12:00:00 AMPNR
Scheduled by a contractor via Hello! on 11/27/2002 at 11:54:32. Contact: ###-####. called left message need to meet with contractor 11/29/2002 2:54:04 PM