Inspections for the day of: Monday, November 29, 2004.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00575 INSP-Final Inspection11/22/200411/29/200411/29/2004 12:00:00 AMAFAIL
Rick, We would like to request meeting at the Hoff building at 9:00am if possible. Please advise us if there is a better time for you. You can reach me here at the office, or on my cell phone at ###-#### as needed. Thank you. Jason; Phone #: ###-#### Internet Inspection Request from: Jason Minnick FACP panel displat not operating; voice page does not tell occupants to exit but to wait at corridors; initiating devices don't match plan addresses; all page microphone not working; BPS one-line diagrams don't match actual wiring; need updated maps 11/29/2004 11:41:38 AM
BLD04-01253 FIRE-Final Inspection11/24/200411/29/200411/29/2004 12:00:00 AMAPASS
Fire/life safety final okay 11/29/2004 11:20:24 AM
FIR04-00332 INSP-Sprinkler Rough-in/Hydro11/29/200411/29/200411/29/2004 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 11/29/2004 at 9:37:31 AM. Contact: ###-####. There is lack of coverage between the glass and the fire shutter at the service counter - the space is 1.5 ft by 15 ft. 11/29/2004 3:46:29 PM
BLD04-00029 FIRE-Final Inspection11/29/200411/29/200411/29/2004 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 11/29/2004 at 9:45:52 AM. Contact: ###-####. Phased project - okay on the 18th floor only 11/29/2004 3:51:18 PM
FIR04-00591 INSP-Final Inspection11/29/200411/29/200411/29/2004 12:00:00 AMPPASS