Inspections for the day of: Monday, November 29, 2004.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00500 INSP-Final Inspection11/24/200411/29/200411/29/2004 12:00:00 AMAPASS
The fire alarm system in the old "E" occupancy has been removed. 11/29/2004 10:25:51 AM
FIR04-00703 INSP-Sprinkler Rough-in/Hydro11/26/200411/29/200411/29/2004 12:00:00 AMAPASS
Sprinkler piping rough-in is ok. Piping is ok to cover 11/29/2004 3:06:09 PM
MIS04-00325 FIR-Final11/26/200411/29/200411/29/2004 12:00:00 AMAPART
A temporary occupancy was given until all of the fire extinguishers have been reinspected, thumbturns removed from basement exit doors and the basement exit sign is fixed 11/29/2004 9:25:38 AM
FIR04-00604 INSP-Sprinkler Rough-in/Hydro11/29/200411/29/200411/29/2004 12:00:00 AMPPASS
Hydro test on the new antifreeze loop is ok. Sprinkler rough-in is ok. There are still items that need to be completed at the final such as forward flush and alarm connections. Piping size on plans as compared to hydraulic calculations does not match. Per bill alexander what has been installed is ok. 11/29/2004 3:09:18 PM
FIR04-00368 INSP-Conference11/29/200411/29/200411/29/2004 12:00:00 AMPDONE
I did a tenting inspection for jack on the fourth floor. I found three locations where piping did not have tenting. Jack will fix. Still does not have letter from structural engineer so no approval for cover given. 11/29/2004 4:03:15 PM
MIS04-00300 FIR-Conference11/29/200411/29/200411/29/2004 12:00:00 AMPPART
A temporary occupancy was given until the existing exit light is repaired 11/29/2004 3:06:49 PM
BLD04-02507 BLD-Conference11/29/200411/29/200411/29/2004 12:00:00 AMPDONE
I spoke with the electrician about the requirement for exit discharge lighting and that the existing emergency light that is in the storage area would be ok to remain without adding additional lighting. I also spoke with the superintendant about door hardware
MIS04-00312 FIR-Final11/29/200411/29/200411/29/2004 12:00:00 AMPPART
A temporary occupancy was given. Need three exit signs repaired. Provide annual inspection for the fire extinguishers. Provide emergency lighting as discussed. Remove deadbolt on rear door. Sprinkler pendants in the west side office are obstructed by walls and pendants in south corridor are less than 6' apart.