FIR05-00198
| INSP-Final Inspection | 11/28/2005 | 11/29/2005 | 11/30/2005 5:36:25 PM | A | DEFR |
|
|
linda; Phone #: ###-#### Per conversation with Linda the inspection will be scheduled for Monday 12/5 as agreed.
|
FIR05-00404
| INSP-Sprinkler Rough-in/Hydro | 11/28/2005 | 11/29/2005 | 11/30/2005 12:57:11 PM | A | PART |
|
|
c/n items have been completed, overhead rough-in is good for cover on the 1st and 2nd floors only, will need to inspect insulation for the 3rd floor prior to cover.
|
MIS05-00097
| FIR-Final | 11/28/2005 | 11/29/2005 | 11/30/2005 12:37:22 PM | P | FAIL |
|
|
Need to provide signage above the main door as discussed, need to post address numbers as required.
|
BLD04-02970
| FIRE-Final Inspection | 11/28/2005 | 11/29/2005 | 11/30/2005 9:58:56 AM | A | PASS |
|
|
Fire life safety approved on 6/13/05.
|
FIR05-00609
| INSP-Final Inspection | 11/29/2005 | 11/29/2005 | 11/29/2005 4:09:57 PM | P | DEFR |
|
|
Need updated plans showing added strobe, will verify supply air has been ducted to avoid mixing air in return at final inspection.
|
FIR05-00366
| INSP-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 4:05:27 PM | P | PASS |
|
|
The two phase project for demo has been completed and passed inspection, permit finaled.
|
FIR05-00729
| INSP-Sprinkler Rough-in/Hydro | 11/28/2005 | 11/29/2005 | 11/29/2005 3:45:44 PM | A | CANC |
|
|
Inspection to be completed 11/30
|
FIR05-00675
| INSP-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 3:37:45 PM | A | FAIL |
|
|
Notification devices in the tenant space are not synchronized with the devices in the common areas, duct detectors tested okay.
|
BLD05-02358
| FIRE-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 2:59:41 PM | A | PART |
|
|
Fire life safety is satisfactory, final pending shell permit finals.
|
FIR05-00643
| INSP-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 2:39:49 PM | A | CANC |
|
|
To be rescheduled for 11/30 in the am.
|
BLD04-02676
| FIRE-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 2:37:22 PM | A | CANC |
|
|
To be rescheduled for 11/30 in the am.
|
BLD05-02017
| FIRE-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 12:07:47 PM | A | PASS |
|
|
c/n items have been completed, fire life safety passed.
|
BLD05-02311
| FIRE-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 11:59:05 AM | A | FAIL |
|
|
The related fire alarm must be accepted prior to final for life safety.
|
FIR05-00636
| INSP-Alarm Testing | 11/28/2005 | 11/29/2005 | 11/29/2005 11:57:11 AM | A | FAIL |
|
|
One notification device at the reception desk/ lobby is not installed as shown on approved plans causing a lack of coverage for this area.
|
BLD05-02211
| FIRE-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 11:54:58 AM | A | PASS |
|
|
Fire life safety is satisfactory.
|
BLD05-01986
| FIRE-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 11:54:14 AM | A | PASS |
|
|
Fire life safety passed inspection.
|
BLD05-02334
| FIRE-Conference | 11/28/2005 | 11/29/2005 | 11/29/2005 11:27:08 AM | A | DONE |
|
|
On site visit regarding drive through canopy fire sprinkler coverage.
|
FIR05-00682
| INSP-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 10:56:34 AM | A | PASS |
|
|
Fire sprinkler work is acceptable, permit finaled.
|
FIR05-00410
| INSP-Sprinkler Rough-in/Hydro | 11/28/2005 | 11/29/2005 | 11/29/2005 10:06:20 AM | A | FAIL |
|
|
The installation appears satisfactory, however, no approved plans were available on site for review or verification. Final will require stamped plans and notes on site for inspection, will also need ceiling tile and canopies installed.
|
BLD05-01736
| FIRE-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 9:29:04 AM | A | FAIL |
|
|
Provide max occupant load sign as indicated on review notes, remove manual thumbturn on the NW exit door, provide the correct length sample tube for the duct detector above the kitchen area.
|
FIR05-00789
| INSP-Final Inspection | 11/28/2005 | 11/29/2005 | 11/29/2005 9:24:10 AM | A | PASS |
|
|
The hood suppression system operated correctly under test conditions, inspection passed.
|
BLD05-01831
| FIRE-Final Inspection | 11/29/2005 | 11/29/2005 | 11/29/2005 12:00:00 AM | A | PASS |
|
|
Fire life safety passed inspection.
|