Inspections for the day of: Wednesday, November 29, 2006.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-03114 ELE-Aging Inspection11/29/200611/29/200612/4/2006 4:00:54 PM DONE
see final
ELE06-03247 ELE-Aging Inspection11/29/200611/29/200612/4/2006 10:12:27 AM DONE
looked at sign, see final
ELE06-03780 Final11/29/200611/29/200611/29/2006 4:05:37 PMPPASS
jack ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, ok to final
ELE06-04207 Final11/28/200611/29/200611/29/2006 3:50:21 PMPPART
scott ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith met contr, wrote corr notice, nec 110.26(F)(1) there shall be no foreign piping systems in dedicated space over panel, rest ok , signed t/o card
ELE06-03714 Electrical Rough-In11/28/200611/29/200611/29/2006 2:58:23 PMPPART
matt; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles ok to cover - but need to see boxes before devices installed in ceiling and walls
ELE06-02075 Final11/29/200611/29/200611/29/2006 1:14:54 PMPFAIL
scott; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles called contr, left corr notice, nec 348.30 fmc shall be secured within 12" of box and not over 6' in length, 410.30(C)(1) cord connected fixtures shall be directly below outlet
ELE06-03490 Final11/29/200611/29/200611/29/2006 12:46:09 PMPPASS
ok to final, signed occ card, found listing on units
ELE06-03797 Electrical Rough-In11/29/200611/29/200611/29/2006 12:44:58 PMPPART
###-#### - paul Note: ceiling and sign temp occ also need to see beds, signed t/o card
ELE06-04382 Rough-In Permanent Service11/29/200611/29/200611/29/2006 12:00:22 PMAPASS
Scheduled by a contractor via Hello! on 11/29/2006 at 6:11:31 AM. Contact: ###-####. ric ok, p/s u/g n ok
ELE06-03089 Rough-In Permanent Service11/27/200611/29/200611/29/2006 9:59:02 AMACANC
joe ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith did combination of ri and final- see final
ELE06-03089 Final11/29/200611/29/200611/29/2006 9:58:10 AMAPASS
joe ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ok to final
ELE06-03931 Rough-In Permanent Service11/28/200611/29/200611/29/2006 9:34:12 AMACANC
bob - note: suites 3 and 4; Phone #: ###-#### x 204 Internet Inspection Request from: Patricia Smith wrong type insp, see ps
ELE06-04333 Final11/28/200611/29/200611/29/2006 9:18:59 AMAPASS
ron ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith looked at sign ok to final
ELE06-03931 Permanent Service11/29/200611/29/200611/29/2006 9:03:14 AMAPASS
bob - note: suites 3 and 4; Phone #: ###-#### x 204 Internet Inspection Request from: Patricia Smith p/s exst meter pak, 2 meters, n, ok
ELE06-04399 Electrical Rough-In11/28/200611/29/200611/29/2006 8:12:04 AMAPART
Phone #: ###-#### Internet Inspection Request from: Tina Payne front 1/2 walls only ok to cover