Inspections for the day of: Thursday, November 29, 2007.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-01371 Final11/28/200711/29/200711/29/2007 4:13:06 PMPFAIL
CARL Phone #: ###-#### met owner, left correction notice, nec 408.4 circuit directory shall be complete, clear and concise for each circuit, 312.5 abrasion protection shall be provided for all conductors entering enclosure ( gec), 110.12(A) all unused openings shall be closed, in panel ( breaker blanks), 210.70(A)(2)(c) shall provide lighting switch at top of stairs and at bottom
ELE07-03671 Final11/29/200711/29/200711/29/2007 3:22:03 PMPPASS
Kevin Brovetto Electrician Phone #: ###-#### Internet Inspection Request from: Jim Burnette ok to final, signed structural card
ELE07-03945 Final11/29/200711/29/200711/29/2007 2:37:00 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Kerri Hamilton ok to final, no card, already signed for occupancy
ELE07-03933 Electrical Rough-In11/29/200711/29/200711/29/2007 1:57:10 PMPPASS
Call Stan Olivia ###-#### for access. He will be home this pm for you.
Phone #: ###-#### Internet Inspection Request from: BRENDA HURST ric ok
ELE07-03933 Final11/29/200711/29/200711/29/2007 1:52:11 PMPPASS
Call Stan Olivia ###-#### for access. He will be home this pm for you.
Phone #: ###-#### Internet Inspection Request from: BRENDA HURST ok to final
ELE07-03955 Permanent Service11/29/200711/29/200711/29/2007 1:31:33 PMPPASS
chuck Phone #: ###-#### p/s u/g rec ok
ELE07-03670 Final11/29/200711/29/200711/29/2007 12:34:24 PMPPASS
Kevin Brovetto Electrician Phone #: ###-#### Internet Inspection Request from: Jim Burnette ok to final, signed structural card
ELE07-02885 Permanent Service11/28/200711/29/200711/29/2007 10:29:59 AMAPASS
pat - please call 1/2 hr prior to inspection Phone #: ###-#### p/s u/g rec ok
ELE07-00573 Conference11/28/200711/29/200711/29/2007 10:05:31 AMADONE
Scheduled by a contractor via Hello! on 11/28/2007 at 3:29:58 PM. Contact: ###-####. met gen contr, x-ray man, talked about listing for x-ray machine, he will let 324 know if ok via UL.
ELE07-02992 Final11/28/200711/29/200711/29/2007 9:36:04 AMAPASS
TIM Phone #: ###-#### called contractor, ok to final
ELE07-02790 Electrical Rough-In11/28/200711/29/200711/29/2007 8:11:40 AMAPASS
Swimming Pool Bonding Grid Inspection. Please call Rowdy with questions @ ###-#### Phone #: ###-#### Internet Inspection Request from: Rowdy Monroe ok to pour equipotential plane only