ELE16-03846
| Temporary Service | 11/29/2016 | 11/29/2016 | 11/29/2016 2:39:03 PM | P | PASS |
|
|
Temp service t/s o/h n ok
|
ELE16-03859
| Electrical Rough-In | 11/28/2016 | 11/29/2016 | 11/29/2016 12:01:45 PM | A | PASS |
|
|
need cover for walls in kitchen and bathroom area call serigo @968 8125 if needed for access but back door should be open Phone #: ###-#### Inspection requested via web by dennis mcneely Kitchen and laundry only ok cover Contractor will assume responsibility for work, owner did say he was not going to flip home.
|
ELE16-03846
| Temporary Service | 11/29/2016 | 11/29/2016 | 11/29/2016 10:19:10 AM | A | FAIL |
|
|
address on temp pole Phone #: ###-#### Inspection requested via web by Mike Swift 250 Main bonding jumper required
|
ELE16-02600
| Electrical Rough-In | 11/28/2016 | 11/29/2016 | 11/29/2016 9:33:21 AM | A | PASS |
|
|
Dave. 5th floor capitol corridor. Phone #: ###-#### Inspection requested via web by Sean DeLacy 5th floor capitol blvd corridor hard lids ok cover
|
ELE16-03800
| Final | 11/28/2016 | 11/29/2016 | 11/29/2016 9:06:52 AM | A | FAIL |
|
|
power is on Phone #: ###-#### Inspection requested via web by Bryan McLaughlin Shall isolate grounding and grounded conductor in sub-panel
|
ELE16-03728
| Electrical Rough-In | 11/28/2016 | 11/29/2016 | 11/29/2016 8:47:07 AM | A | PASS |
|
|
Ready for underground inspection. Please check bonding of rebar for block wall. Think it was inspected with bonding inspection but wanted to double check. Thank You Phone #: ###-#### Inspection requested via web by Kelly Felin Pool underground ok cover, Bonding was previously inspected and is ok.
|