Inspections for the day of: Tuesday, November 29, 2016.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-01381 FIRE-Final Inspection11/28/201611/29/201611/29/2016 3:03:47 PMAPASS
life safety passed
FIR16-00364 INSP-Final Inspection11/29/201611/29/201611/29/2016 3:00:27 PMPCANC
Rescheduled for tomorrow as previously discussed. calvin Phone #: ###-####
BLD16-02213 FIRE-Final Inspection11/28/201611/29/201611/29/2016 2:45:46 PMPFAIL
Provide sprinkler modifications or baffle as discussed, provide documentation that the emergency light in the kitchen can be deleted. Exit discharge lights repaired as I waited.
BLD16-03872 FIRE-Final Inspection11/28/201611/29/201611/29/2016 2:43:32 PMAPASS
Life safety passed. TVFP is going to do the annual inspection
FIR16-00540 INSP-Final Inspection11/28/201611/29/201611/29/2016 2:40:47 PMPCANC
Robert Phone #: ###-####
BLD16-00731 FIRE-Final Inspection11/28/201611/29/201611/29/2016 2:40:31 PMPPASS
Life safety passed
FIR16-00435 INSP-Final Inspection11/29/201611/29/201611/29/2016 2:39:51 PMPPASS
Permit finaled
BLD16-03620 FIRE-Final Inspection11/28/201611/29/201611/29/2016 10:42:57 AMAPASS
Life safety passed
FIR16-00284 INSP-Sprinkler Rough-in11/28/201611/29/201611/29/2016 10:08:26 AMAPART
Two of the north side, second floor apartments are ok to cover the other two need tenting corrected. Also the north end east side stairwell piping has not been tented yet. See the city approved plans for locations marked.
FIR16-00540 INSP-Sprinkler Rough-in11/28/201611/29/201611/29/2016 9:21:24 AMAFAIL
Two pendants need to be added in the Bakery Area. Fire dept needs to approve the location/blockage of the FDC.
FIR16-00540 INSP-Sprinkler Rough-in/Hydro11/28/201611/29/201611/29/2016 9:20:34 AMAFAIL
Can not due hydro because of the two heads that need to be added in the Bakery Area.
FIR16-00364 INSP-Final Inspection11/28/201611/29/201611/29/2016 9:19:35 AMAPART
Sprinkler work complete in apartments 101, 102, 201, 202, 301, 302.
BLD14-03070 FIRE-Final Inspection11/23/201611/29/201611/29/2016 9:18:49 AMAPART
Life safety passed only for apartments 101, 102, 201, 202, 301, 302.
FIR16-00254 INSP-Final Inspection11/23/201611/29/201611/29/2016 9:17:55 AMAPASS
Permit finaled