Inspections for the day of: Wednesday, November 29, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03784 Electrical Rough-In11/28/201711/29/201711/29/2017 3:01:07 PMPPASS
Wall and ceiling rough-in Phone #: ###-#### Inspection requested via web by Debby Pierce
Vehicle blocked in due to all entrances closed up so landscaping around perimeter could be completed. Over 30 minutes before George was able to clear path. Will call to make sure entrance and exit will remain clear. Inspection will fail if access is not available.
Wall rough in ok cover
ELE17-03957 Electrical Rough-In11/28/201711/29/201711/29/2017 1:35:52 PMPPART
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Island wall not ready yet, left open for lift access. Panel wall only rough in ok cover
ELE17-02732 Electrical Rough-In11/28/201711/29/201711/29/2017 1:21:25 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
All grid except IT room and east side as noted on contractor print rough in ok cover
ELE17-02726 Final11/28/201711/29/201711/29/2017 11:15:37 AMAFAIL
Code 2010 Phone #: ###-#### Inspection requested via web by danny perrine
110.22- Furnace disconnect shall be so identified and on/off shall be identified.
422.12- Central heating appliance shall be on a dedicated branch circuit. When furnace breaker off opener receptacles went off.










422.12- Central heating appliance shall be on indvidual branch circuit. Garage door receptacles went off when furnace breaker turned off.
ELE17-03982 Temporary Service11/28/201711/29/201711/29/2017 10:03:08 AMAFAIL
Phone #: ###-#### Inspection requested via web by Darryn Coburn
110.14- Grounding electrode terminal corroded. Will not tighten down on wire.
ELE17-03980 Rough-In Permanent Service11/28/201711/29/201711/29/2017 9:48:30 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Check on final 408.41 grounded terminations shall be individual.
Rough in ok cover p/s u/g n ok
ELE17-03059 Final11/29/201711/29/201711/29/2017 9:34:14 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Final ok
ELE17-03349 Final11/28/201711/29/201711/29/2017 9:08:56 AMAPASS
garage code 2468 Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok