Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-04610 Temporary Service11/27/201911/29/201911/29/2019 9:54:18 AMACANC
Phone #: ###-#### Inspection requested via web by Louis Keller
Needed partial final
ELE19-04610 Final11/29/201911/29/201911/29/2019 9:54:00 AMPPART
Phone #: ###-#### Inspection requested via web by Louis Keller
Two 3-pole 60 amp circuits added for additional fryers with receptacles. As per 210.8(B) all receptacle outlets measuring 150 volts or less to ground, 100 amps or less installed in a commercial kitchen shall have GFCI protection. At time of inspection GFCI protection for personel not in place on these new circuits. For TCO contractor for ELE19-03585 other permit for this remodel has provided lock outs for these circuits. As per Daryl DeGrange Chief Electrical inspector this is acceptable for TCO. TCO ok
ELE19-03585 Conference11/29/201911/29/201911/29/2019 9:53:32 AMPDONE
Discussed options for providing GFCI protection for 2 additional circuits added for fryers.
1- GFCI protection built into a circuit breaker
(apparently not available).
2- In line GFCI products are available.
3- Shunt trip circuitry available.
For Final a second permit exists for other contractor. ELE19-04610.
ELE19-04461 Final11/27/201911/29/201911/29/2019 9:07:19 AMAPASS
Code for the back door is 2100. No one is living there. Phone #: ###-#### Inspection requested via web by Barbara Szurgot
Carport and mud room Final ok