ELE19-04610
| Temporary Service | 11/27/2019 | 11/29/2019 | 11/29/2019 9:54:18 AM | A | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Louis Keller Needed partial final
|
ELE19-04610
| Final | 11/29/2019 | 11/29/2019 | 11/29/2019 9:54:00 AM | P | PART |
|
|
Phone #: ###-#### Inspection requested via web by Louis Keller Two 3-pole 60 amp circuits added for additional fryers with receptacles. As per 210.8(B) all receptacle outlets measuring 150 volts or less to ground, 100 amps or less installed in a commercial kitchen shall have GFCI protection. At time of inspection GFCI protection for personel not in place on these new circuits. For TCO contractor for ELE19-03585 other permit for this remodel has provided lock outs for these circuits. As per Daryl DeGrange Chief Electrical inspector this is acceptable for TCO. TCO ok
|
ELE19-03585
| Conference | 11/29/2019 | 11/29/2019 | 11/29/2019 9:53:32 AM | P | DONE |
|
|
Discussed options for providing GFCI protection for 2 additional circuits added for fryers. 1- GFCI protection built into a circuit breaker (apparently not available). 2- In line GFCI products are available. 3- Shunt trip circuitry available. For Final a second permit exists for other contractor. ELE19-04610.
|
ELE19-04461
| Final | 11/27/2019 | 11/29/2019 | 11/29/2019 9:07:19 AM | A | PASS |
|
|
Code for the back door is 2100. No one is living there. Phone #: ###-#### Inspection requested via web by Barbara Szurgot Carport and mud room Final ok
|