Inspections for the day of: Monday, November 3, 2003.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE03-03463 Final10/31/200311/3/200311/3/2003 12:00:00 AMACANC
###-#### Ron see added r/i 11/3/2003 12:57:04 PM
ELE03-03465 Final10/31/200311/3/200311/3/2003 12:00:00 AMACANC
###-#### Chris Carmine. will inspect in the PM 11/3/2003 9:23:08 AM
ELE03-03200 Electrical Rough-In10/31/200311/3/200311/3/2003 12:00:00 AMAPART
tom; Phone #: ###-#### Internet Inspection Request from: Darla Downs N half 4th floor walls 11/3/2003 10:48:37 AM
ELE03-03460 Permanent Service10/31/200311/3/200311/3/2003 12:00:00 AMAPASS
scott; Phone #: ###-#### Internet Inspection Request from: Darla Downs
p/s o/h rec. ok 11/3/2003 9:23:44 AM
ELE03-03462 Rough-In Permanent Service10/31/200311/3/200311/3/2003 12:00:00 AMAPASS
###-#### Ron r/i ok
p/s u/g new ok 11/3/2003 10:48:04 AM
ELE03-02683 Electrical Rough-In10/31/200311/3/200311/3/2003 12:00:00 AMPPART
contact: Tom Betty Underground inspection; Phone #: ###-#### Internet Inspection Request from: Deb McCoy ok 11/3/2003 4:18:07 PM
ELE03-02975 Electrical Rough-In11/3/200311/3/200311/3/2003 12:00:00 AMPPART
Paul; Phone #: ###-#### Internet Inspection Request from: Aimee Hughes 2nd floor only ok 11/3/2003 3:49:34 PM
ELE03-03472 Rough-In Permanent Service11/3/200311/3/200311/3/2003 12:00:00 AMPFAIL
###-#### chris cor. posted called 300.4 11/4 and nail plates 250.66 needs #4 grd to rebar 11/3/2003 1:52:06 PM
ELE03-02733 Electrical Rough-In11/3/200311/3/200311/3/2003 12:00:00 AMPPART
Phone #: ###-#### Internet Inspection Request from: Jeff Radford u/g 11/3/2003 2:24:07 PM
ELE03-03465 Final11/3/200311/3/200311/3/2003 12:00:00 AMPCANC
see added r/i 11/3/2003 12:24:01 PM
ELE03-03465 Electrical Rough-In11/3/200311/3/200311/3/2003 12:00:00 AMPPASS
walls ok
ELE03-03463 Electrical Rough-In11/3/200311/3/200311/3/2003 12:00:00 AMPFAIL
cor. posted called left message 314.16 box fill cutin box?, 314.43 no screws inside plastic boxes, 210.52(ABC) outlet spacing walls , check kit circuits,, need to talk with contractor