Inspections for the day of: Monday, November 3, 2003.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00480 INSP-Sprinkler Rough-in10/31/200311/3/200311/3/2003 12:00:00 AMAPART
inspection was for hangers in the fire sprinkler riser room. Hangers are ok to fire proof 11/3/2003 12:20:03 PM
BLD03-00497 FIRE-Final Inspection10/31/200311/3/200311/3/2003 12:00:00 AMAPASS
fire life safety finaled 11/4/2003 9:47:55 AM
BLD03-01004 FIRE-Final Inspection10/31/200311/3/200311/3/2003 12:00:00 AMAPASS
fire sprinkler and fire life safety finaled 11/4/2003 9:49:06 AM
FIR03-00206 INSP-Sprinkler Rough-in/Hydro11/3/200311/3/200311/3/2003 12:00:00 AMPPART
sprinklers are ok to cover in the round chapel area in the connection between the new church and the existing area 11/3/2003 2:42:22 PM
FIR03-00388 INSP-Final Inspection10/29/200311/3/200311/3/2003 12:00:00 AMPFAIL
relocate the a/v in the lobby so lense is between 80 and 96 inches, sync strobes in lobby area. 11/3/2003 3:18:02 PM