FIR04-00546
| INSP-Sprinkler Rough-in/Hydro | 11/2/2004 | 11/3/2004 | 11/3/2004 12:00:00 AM | P | PART |
|
|
Overhead sprinkler piping in the remodeled classrooms and the new wing is ok. A second inspection will be needed for piping to pendants. There a pipe sizes installed that do not match approved plans as well as pendants installed in areas not shown to have ceilings. Resubmit plans to city of boise for approval showing ceilings and actual pipe sizes 11/3/2004 4:14:13 PM
|
BLD04-00871
| FIRE-Conference | 11/3/2004 | 11/3/2004 | 11/3/2004 12:00:00 AM | P | DONE |
|
|
I spoke to the fire alarm contractor about separate annunciation for the backflow preventor and placement of the horn. 11/3/2004 3:09:12 PM
|
FIR04-00504
| INSP-Final Inspection | 11/3/2004 | 11/3/2004 | 11/3/2004 12:00:00 AM | P | PASS |
|
|
Fire sprinklers finaled 11/3/2004 3:07:21 PM
|
BLD04-00350
| FIRE-Final Inspection | 11/3/2004 | 11/3/2004 | 11/3/2004 12:00:00 AM | P | FAIL |
|
|
Doors to apartments 102, 103, 106, 108 and 208 do not close and latch. Smoke detector in bedroom of apartment 107 does not ativate the kitchen smoke detector. Provide verification that the smoke detector in handi-cap room 105 is photo since there is no silence button. 11/3/2004 1:31:00 PM
|
BLD04-00350
| FIRE-Alarm Testing | 11/3/2004 | 11/3/2004 | 11/3/2004 12:00:00 AM | P | CANC |
|
|
Duplicate inspection 11/3/2004 1:31:11 PM
|
FIR04-00568
| INSP-Final Inspection | 11/3/2004 | 11/3/2004 | 11/3/2004 12:00:00 AM | P | PASS |
|
|
Hood suppression system operated correctly 11/3/2004 3:06:57 PM
|