Inspections for the day of: Wednesday, November 3, 2004.
Number of inspections: 6
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00546 INSP-Sprinkler Rough-in/Hydro11/2/200411/3/200411/3/2004 12:00:00 AMPPART
Overhead sprinkler piping in the remodeled classrooms and the new wing is ok. A second inspection will be needed for piping to pendants. There a pipe sizes installed that do not match approved plans as well as pendants installed in areas not shown to have ceilings. Resubmit plans to city of boise for approval showing ceilings and actual pipe sizes 11/3/2004 4:14:13 PM
BLD04-00871 FIRE-Conference11/3/200411/3/200411/3/2004 12:00:00 AMPDONE
I spoke to the fire alarm contractor about separate annunciation for the backflow preventor and placement of the horn. 11/3/2004 3:09:12 PM
FIR04-00504 INSP-Final Inspection11/3/200411/3/200411/3/2004 12:00:00 AMPPASS
Fire sprinklers finaled 11/3/2004 3:07:21 PM
BLD04-00350 FIRE-Final Inspection11/3/200411/3/200411/3/2004 12:00:00 AMPFAIL
Doors to apartments 102, 103, 106, 108 and 208 do not close and latch. Smoke detector in bedroom of apartment 107 does not ativate the kitchen smoke detector. Provide verification that the smoke detector in handi-cap room 105 is photo since there is no silence button. 11/3/2004 1:31:00 PM
BLD04-00350 FIRE-Alarm Testing11/3/200411/3/200411/3/2004 12:00:00 AMPCANC
Duplicate inspection 11/3/2004 1:31:11 PM
FIR04-00568 INSP-Final Inspection11/3/200411/3/200411/3/2004 12:00:00 AMPPASS
Hood suppression system operated correctly 11/3/2004 3:06:57 PM