Inspections for the day of: Thursday, November 3, 2005.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR05-00459 INSP-Alarm Testing11/2/200511/3/200511/4/2005 10:02:08 AMPFAIL
Tested theatres, need to retest two EOL , add speaker in theatre 3, still need to test and verify correct locations for duct detectors, see correction notice for listing of remaining items, final inspection not approved at this time.
BLD05-01669 FIRE-Conference11/3/200511/3/200511/3/2005 4:37:26 PMPDONE
On site discussion with Ben regarding insulation issues as they affect fire sprinklers in the attic and dormer areas.
FIR05-00326 INSP-Supply line flush11/2/200511/3/200511/3/2005 4:35:22 PMPFAIL
Provide resubmittals as required indicating information as requested on plan review notes and all field changes from original plans, overhead inspection failed due to numerous issues including spacing, head temps., bracing, seismic clearance, obstructions to discharge, riser not complete, etc., the UG was flush was performed and is acceptable.
FIR05-00174 INSP-Final Inspection11/3/200511/3/200511/3/2005 2:02:06 PMPCANC
Wrong permit number called in, this inspection was for overhead cover on permit FIR05-00405 bld #13.
MIS05-00194 FIR-Final11/3/200511/3/200511/3/2005 1:26:43 PMPPASS
Life safety passed inspection.
FIR05-00385 INSP-Sprinkler Rough-in11/3/200511/3/200511/3/2005 12:54:03 PMPPART
The 3rd floor center common area hard lid area is acceptable for cover, also discussed coverage requirements for small room at perimeter and 2nd floor hard lid areas.
BLD05-00672 FIRE-Final Inspection11/2/200511/3/200511/3/2005 11:04:19 AMANR
Fire sprinkler permit must be finaled prior to life safety sign-off.
BLD04-01324 FIRE-Final Inspection11/2/200511/3/200511/3/2005 10:13:40 AMAFAIL
Emergency lighting and exit signs in several locations are not functional, exit doors at north and west sides are not installed yet, some exit discharge lighting is not installed on the east and south sides, fire lane marking remains to be completed, not all items reviewed at this inspection.
FIR05-00405 INSP-Sprinkler Rough-in11/3/200511/3/200511/3/2005 12:00:00 AMPPART
Insulation tenting at 3rd floor is acceptable, okay to cover, "blown in" insulation to be done after lid is sheetrocked.