FIR05-00701
| INSP-Final Inspection | 11/3/2005 | 11/3/2005 | 11/3/2005 3:39:15 PM | P | PASS |
|
|
Permit finaled
|
FIR05-00523
| INSP-Sprinkler Rough-in/Hydro | 11/2/2005 | 11/3/2005 | 11/3/2005 3:38:53 PM | A | FAIL |
|
|
Anti-freeze loop hydro test failed twice today.
|
BLD05-01399
| FIRE-Final Inspection | 11/2/2005 | 11/3/2005 | 11/3/2005 1:56:12 PM | A | PASS |
|
|
Life safety passed
|
FIR05-00180
| INSP-Final Inspection | 11/1/2005 | 11/3/2005 | 11/3/2005 1:32:56 PM | A | FAIL |
|
|
Signals are still incorrect. Duct detector for hvac unit 10 comes in as dry system tamper. I need verification that all signals have been verified for all devices on the fire alarm system. Re-inspection fee required before the next inspeciton.
|
BLD04-00725
| FIRE-Final Inspection | 11/2/2005 | 11/3/2005 | 11/3/2005 1:27:50 PM | A | FAIL |
|
|
No inspection done due to the fire alarm being failed and building issues noted. The building issues noted include tenting/canopy materials enclosing the south canopy. This area is shown on the building plans as being enclosed with walls. A permit is needed for the canopy and the two heaters, bbq and the space LP tanks removed. Plans need to be resubmitted to show this work removed or the work needs to be completed. A ceiling needs to be installed in the fire sprinkler riser room to cover the exposed cpvc sprinkler piping. The accelerator on the dry pipe valve has a sign stating the it does not work and the trim valves to it are closed. This device needs to be repaired.
|
BLD05-02196
| FIRE-Final Inspection | 11/1/2005 | 11/3/2005 | 11/3/2005 10:53:29 AM | A | PASS |
|
|
Life safety finaled
|
BLD05-02237
| FIRE-Final Inspection | 11/2/2005 | 11/3/2005 | 11/3/2005 10:42:46 AM | A | PASS |
|
|
life safety finaled
|
BLD05-02791
| FIRE-Final Inspection | 11/3/2005 | 11/3/2005 | 11/3/2005 10:09:35 AM | P | PASS |
|
|
life safety passed
|
FIR05-00672
| INSP-Alarm Testing | 11/2/2005 | 11/3/2005 | 11/3/2005 9:59:40 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Wayne Berry
|
FIR05-00672
| INSP-Final Inspection | 11/3/2005 | 11/3/2005 | 11/3/2005 9:59:24 AM | P | PASS |
|
|
pemit finaled
|
FIR05-00673
| INSP-Final Inspection | 11/1/2005 | 11/3/2005 | 11/3/2005 9:58:08 AM | A | PASS |
|
|
permit finaled
|
BLD05-02602
| FIRE-Final Inspection | 11/2/2005 | 11/3/2005 | 11/3/2005 9:57:40 AM | A | PASS |
|
|
Life safety finaled
|
FIR05-00607
| INSP-Final Inspection | 11/3/2005 | 11/3/2005 | 11/3/2005 9:56:44 AM | P | PASS |
|
|
permit finaled
|
FIR05-00607
| INSP-Alarm Testing | 11/2/2005 | 11/3/2005 | 11/3/2005 9:46:45 AM | A | PASS |
|
|
permit finaled
|
FIR05-00607
| INSP-Final Inspection | 11/3/2005 | 11/3/2005 | 11/3/2005 12:00:00 AM | P | PASS |
|
|
permit finaled
|