FIR08-00424
| INSP-Sprinkler Rough-in/Hydro | 11/3/2008 | 11/3/2008 | 11/3/2008 4:00:37 PM | P | DEFR |
|
|
Site work is incomplete.
|
FIR08-00618
| INSP-Final Inspection | 11/3/2008 | 11/3/2008 | 11/3/2008 3:55:18 PM | P | FAIL |
|
|
Need to provide signage at the door to the relocated FACP room, missing three junction box covers-two at the 2nd floor one at the 1st floor, noted the outside sprinkler waterflow bell is not functional. Notification, manual pulls, signals recieved, nac and main panel tested okay.
|
FIR08-00713
| INSP-Final Inspection | 11/3/2008 | 11/3/2008 | 11/3/2008 3:50:39 PM | P | FAIL |
|
|
Noted two non-functional horn/strobe notification devices at the 2nd floor sales area.
|
FIR08-00596
| INSP-Sprinkler Rough-in/Hydro | 11/3/2008 | 11/3/2008 | 11/3/2008 3:48:54 PM | P | PART |
|
|
Okay for cover at the 2nd floor office room ceiling.
|
BLD08-00942
| FIRE-Final Inspection | 11/3/2008 | 11/3/2008 | 11/3/2008 2:41:56 PM | P | PART |
|
|
Project related fire sprinkler permit work has been finaled.
|
FIR06-00595
| INSP-Final Inspection | 11/3/2008 | 11/3/2008 | 11/3/2008 12:13:05 PM | P | PART |
|
|
C/N items finished, record of completion forms to be submitted as discussed.
|
BLD07-03106
| FIRE-Final Inspection | 10/30/2008 | 11/3/2008 | 11/3/2008 12:08:23 PM | A | PASS |
|
|
Items on correction notice verified for completion, life safety inspection passed.
|
BLD08-02330
| FIRE-Final Inspection | 10/31/2008 | 11/3/2008 | 11/3/2008 11:50:45 AM | A | FAIL |
|
|
Post address numbers at suite 184 per review comments, visual lock indicator at the main entry/exit ste 184 needs to be moved to the egress side per IFC 2006.
|