Inspections for the day of: Tuesday, November 3, 2009.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00583 INSP-Conference11/3/200911/3/200911/3/2009 4:12:59 PMPDONE
Regarding location of new notification appliances including H/S and horn only devices.
FIR09-00376 INSP-Conference11/3/200911/3/200911/3/2009 4:11:55 PMPDONE
Regarding requirements per NFPA13 2007 sec. 8.6.7.1 and 8.6.7.2.
BLD09-01640 FIRE-Final Inspection11/3/200911/3/200911/3/2009 4:10:53 PMPPASS
Fire life safety inspection completed acceptable, corrections finished while on site.
BLD09-01337 FIRE-Final Inspection11/3/200911/3/200911/3/2009 4:09:49 PMPNR
Pending project related fire alarm permit work final.
FIR09-00587 INSP-Final Inspection11/3/200911/3/200911/3/2009 4:09:16 PMPFAIL
Noted one overspaced notification device, one obstructed horn/strobe at the engineer room, one existing strobe is mounted too high, per contractor new and existing notification circut appliances are not in synchronization.
FIR09-00418 INSP-Conference11/3/200911/3/200911/3/2009 4:06:27 PMADONE
Regarding fire code review notes items.
FIR09-00625 INSP-Final Inspection11/2/200911/3/200911/3/2009 4:05:22 PMAPASS
Hood suppression system functioned properly under test conditions, contractor to provide separation at fryer and range as discussed.