Inspections for the day of: Tuesday, November 3, 2009.
Number of inspections: 7
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD09-01808 FIRE-Final Inspection11/3/200911/3/200911/3/2009 3:25:40 PMPFAIL
Todays inspection was actually a conference about cover. Sheet rock is ok to be installed by Fire pending the other inspectors approvals.
BLD09-01771 FIRE-Final Inspection11/2/200911/3/200911/3/2009 3:21:07 PMPCANC
chancey Phone #: ###-####
FIR09-00611 INSP-Sprinkler Rough-in11/3/200911/3/200911/3/2009 1:43:42 PMPPASS
Phase 2 sprinkler piping can be covered. Insulation at the deck needs re-attached and will be verified at the building final.
FIR09-00534 INSP-Final Inspection11/3/200911/3/200911/3/2009 1:42:45 PMPFAIL
The general contractor removed ceiling tile.
BLD07-02208 FIRE-Final Inspection11/3/200911/3/200911/3/2009 1:42:04 PMPFAIL
Provide the correct 2A fire extinguishers as discussed. Smoke alarms tested ok.
BLD07-02202 FIRE-Final Inspection11/3/200911/3/200911/3/2009 1:41:48 PMPFAIL
Provide the correct 2A fire extinguishers as discussed. Smoke alarms tested ok.
BLD08-02539 BLD-Aging Inspection11/2/200911/3/200911/3/2009 10:47:00 AMADONE
Fire final inspection is scheduled for tomorrow.