FIR08-00194
| FIR-Aging Inspection | 11/3/2010 | 11/3/2010 | 11/8/2010 3:00:11 PM | | NR |
|
|
I spoke to Dave about getting Rick to set this inspection up.
|
FIR10-00326
| INSP-Final Inspection | 11/3/2010 | 11/3/2010 | 11/4/2010 10:09:09 AM | P | CANC |
|
|
Canceled due to time constraints
|
FIR10-00400
| INSP-Sprinkler Rough-in | 11/2/2010 | 11/3/2010 | 11/3/2010 4:40:28 PM | P | FAIL |
|
|
Plans need to be resubmitted showing all piping changes and additional sprinkler heads. Revised hydraulic calculations are required showing the routing changes and additional fitting added due to structural members. Resubmittals were required per the approved plans if additional fittings or piping were provided. See the city approved plans for locations of deficiencies as marked in red. Two items not marked on the plans but discussed with Bill were the clearance for the main penatrations through the block walls and a letter from a structural engineer or manufacturer addressing/approving the drilling of the structural members to mount the siesmic bracing.
|
FIR10-00400
| INSP-Sprinkler Rough-in/Hydro | 11/2/2010 | 11/3/2010 | 11/3/2010 4:24:44 PM | P | FAIL |
|
|
Duplicate inspection for a hydro. See previous notes.
|
FIR10-00400
| INSP-Supply line flush | 11/2/2010 | 11/3/2010 | 11/3/2010 4:19:17 PM | A | PART |
|
|
The underground hydro test passed. Could not perform above ground hydro tests or flush the underground supply due to not having the main water supply turned on..
|
FIR10-00028
| INSP-Sprinkler Rough-in | 11/2/2010 | 11/3/2010 | 11/3/2010 4:16:46 PM | P | PASS |
|
|
The 24 hour air test passed
|
FIR09-00174
| INSP-Final Inspection | 11/2/2010 | 11/3/2010 | 11/3/2010 10:59:57 AM | A | PASS |
|
|
Permit finaled.
|
BLD10-02101
| FIRE-Final Inspection | 11/3/2010 | 11/3/2010 | 11/3/2010 10:56:44 AM | P | PASS |
|
|
life safety passed
|
BLD10-02100
| FIRE-Final Inspection | 11/3/2010 | 11/3/2010 | 11/3/2010 10:56:22 AM | P | PASS |
|
|
life safety passed.
|
FIR09-00077
| INSP-Final Inspection | 11/2/2010 | 11/3/2010 | 11/3/2010 9:35:25 AM | A | PASS |
|
|
Permit finaled
|
FIR09-00012
| INSP-Final Inspection | 11/2/2010 | 11/3/2010 | 11/3/2010 9:34:26 AM | A | PASS |
|
|
Permit finaled.
|