Inspections for the day of: Wednesday, November 3, 2010.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00194 FIR-Aging Inspection11/3/201011/3/201011/8/2010 3:00:11 PM NR
I spoke to Dave about getting Rick to set this inspection up.
FIR10-00326 INSP-Final Inspection11/3/201011/3/201011/4/2010 10:09:09 AMPCANC
Canceled due to time constraints
FIR10-00400 INSP-Sprinkler Rough-in11/2/201011/3/201011/3/2010 4:40:28 PMPFAIL
Plans need to be resubmitted showing all piping changes and additional sprinkler heads. Revised hydraulic calculations are required showing the routing changes and additional fitting added due to structural members. Resubmittals were required per the approved plans if additional fittings or piping were provided. See the city approved plans for locations of deficiencies as marked in red. Two items not marked on the plans but discussed with Bill were the clearance for the main penatrations through the block walls and a letter from a structural engineer or manufacturer addressing/approving the drilling of the structural members to mount the siesmic bracing.
FIR10-00400 INSP-Sprinkler Rough-in/Hydro11/2/201011/3/201011/3/2010 4:24:44 PMPFAIL
Duplicate inspection for a hydro. See previous notes.
FIR10-00400 INSP-Supply line flush11/2/201011/3/201011/3/2010 4:19:17 PMAPART
The underground hydro test passed. Could not perform above ground hydro tests or flush the underground supply due to not having the main water supply turned on..
FIR10-00028 INSP-Sprinkler Rough-in11/2/201011/3/201011/3/2010 4:16:46 PMPPASS
The 24 hour air test passed
FIR09-00174 INSP-Final Inspection11/2/201011/3/201011/3/2010 10:59:57 AMAPASS
Permit finaled.
BLD10-02101 FIRE-Final Inspection11/3/201011/3/201011/3/2010 10:56:44 AMPPASS
life safety passed
BLD10-02100 FIRE-Final Inspection11/3/201011/3/201011/3/2010 10:56:22 AMPPASS
life safety passed.
FIR09-00077 INSP-Final Inspection11/2/201011/3/201011/3/2010 9:35:25 AMAPASS
Permit finaled
FIR09-00012 INSP-Final Inspection11/2/201011/3/201011/3/2010 9:34:26 AMAPASS
Permit finaled.