ELE15-03543
| Electrical Rough-In | 11/2/2015 | 11/3/2015 | 11/3/2015 2:20:16 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kotton Corder Underground from equipment to pool, Bonds from equipment to pool shell, 4 corners, and cover. Rough in ok cover
|
ELE14-00284
| Final | 11/3/2015 | 11/3/2015 | 11/3/2015 1:49:17 PM | P | PASS |
|
|
Final on Garage 2. Contact Craig Timmons @ ###-#### or Bob Mott. Phone #: ###-#### Inspection requested via web by Cathy Duchek Final ok
|
ELE15-03556
| Temporary Service | 11/3/2015 | 11/3/2015 | 11/3/2015 1:47:00 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE15-03555
| Temporary Service | 11/3/2015 | 11/3/2015 | 11/3/2015 1:22:31 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE15-03557
| Temporary Service | 11/3/2015 | 11/3/2015 | 11/3/2015 12:58:13 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE15-03554
| Temporary Service | 11/3/2015 | 11/3/2015 | 11/3/2015 12:51:34 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn t/s u/g n ok
|
ELE12-01653
| ELE-Aging Inspection | 11/3/2015 | 11/3/2015 | 11/3/2015 12:09:22 PM | | DONE |
|
|
Waiting on contractor to schedule
|
ELE15-03535
| Rough-In Permanent Service | 11/2/2015 | 11/3/2015 | 11/3/2015 10:46:23 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Darryn Coburn 300.4- Where NM cable ran through bored holes that do not maintain 1 1/4" from framing surface thay shall be protected from physical damage by nail plates. 300.5- Underground direct burial conductors shall be protected to a minimum depth shown in 300.5. Job will not pass until temp pole set properly.
|
ELE15-02841
| Final | 11/3/2015 | 11/3/2015 | 11/3/2015 10:04:21 AM | A | PASS |
|
|
Garage code 2020E Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|
ELE15-03508
| Rough-In Permanent Service | 11/2/2015 | 11/3/2015 | 11/3/2015 9:34:16 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn Rough in ok cover p/s u/g n ok
|
ELE15-02611
| Final | 11/2/2015 | 11/3/2015 | 11/3/2015 9:33:02 AM | A | PASS |
|
|
CODE 4224 Phone #: ###-#### Inspection requested via web by Bob Glenn Final ok
|