Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
GCB14-00099 FIRE-Final Inspection11/2/201511/3/201511/4/2015 2:17:17 PMAPASS
Fire Life Safety Pass.

Riser room signage, map at annuciator with FACP and riser call outs and device map at FACP verified
NAF15-00006 INSP-Final11/2/201511/3/201511/4/2015 2:09:08 PMPCANC
Cancelled reschuduled for tomorrow.
NAF15-00014 INSP-Final11/2/201511/3/201511/4/2015 8:09:14 AMACANC
Cancelled per phone call with contractor.
NAF15-00025 INSP-Supply line flush11/3/201511/3/201511/3/2015 10:33:31 AMADONE
Early Start Inspection for riser stub in. Riser ok to pour floor slab, discussed pouring around a ring for seismic protection. Verified appropriate depth on stub outside of building footing. End of pipe submerged in dirt, unsure if capped, ensure flush is done well at later date.
NAF15-00024 INSP-Supply line flush11/2/201511/3/201511/2/2015 4:05:11 PMAPASS
Contractor excavated trench more so that no berm as previously agreed upon would be required. Depth of cover is good, ok to cover.

Pump house has walls, rooft and door. No floor drain as required is installed. Mentioned to Anthony.