Inspections for the day of: Friday, November 30, 2001.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD01-01885 FIRE-Alarm Testing11/27/200111/30/200111/30/2001 12:00:00 AMAPASS
Fire sprinkler, fire alarm finaled. OK for perm occ 11/30/2001 12:58:13 PM
MIS01-00221 FIR-Final11/29/200111/30/200111/30/2001 12:00:00 AMACANC
no corrections made 11/30/2001 2:09:41 PM
FIR01-00587 INSP-Sprinkler Rough-in/Hydro11/29/200111/30/200111/30/2001 12:00:00 AMAPART
Cut back pipe in SE corner head to 7'-6" from draft stop, prove 1" pipe in SE corner, provide verification that hangers mounted to bottom chord is ok. Everything else can be covered. 11/30/2001 10:10:32 AM
FIR01-00475 INSP-Sprinkler Rough-in/Hydro11/29/200111/30/200111/30/2001 12:00:00 AMAPART
AAA Office is OK to cover after additional EQ braces are added. No other areas were inspected 11/30/2001 9:03:44 AM
BLD00-02277 FIRE-Final Inspection11/30/200111/30/200111/30/2001 12:00:00 AMPPASS
Fire sprinkler system finaled. 11/30/2001 1:45:30 PM
BLD01-02423 FIRE-Final Inspection11/30/200111/30/200111/30/2001 12:00:00 AMPFAIL
Repair exit signs, install and test dampers, test door release, get fire extinguishers and fire sprinkler riser inspected, provide emergency light in lobby. 11/30/2001 5:11:52 PM
BLD01-02423 FIRE-Final Inspection11/30/200111/30/200111/30/2001 12:00:00 AMPFAIL
Repair exit signs, install and test dampers, test door release, get fire extinguishers and fire sprinkler riser inspected, provide emergency light in lobby. 11/30/2001 5:11:52 PM
FIR01-00415 INSP-Final Inspection11/30/200111/30/200111/30/2001 12:00:00 AMPFAIL
Provide sign on main exit door "Do not lock", repair exit and emergency lights, relocate one exit light and delete the other in the break room, add one sprinkler head in office, test overhead door. 11/30/2001 5:10:32 PM
FIR01-00415 INSP-Final Inspection11/30/200111/30/200111/30/2001 12:00:00 AMPFAIL
Provide sign on main exit door "Do not lock", repair exit and emergency lights, relocate one exit light and delete the other in the break room, add one sprinkler head in office, test overhead door. 11/30/2001 5:10:32 PM
FIR01-00444 INSP-Final Inspection11/30/200111/30/200111/30/2001 12:00:00 AMPPASS
Fire sprinkler system finaled. OK for perm occ 11/30/2001 10:32:00 AM
FIR01-00571 INSP-Final Inspection11/30/200111/30/200111/30/2001 12:00:00 AMPPASS
Added by Inspector: 430 On 11/30/2001 12:54:51 PM Fire alarm finaled. OK for perm occ.
FIR01-00290 INSP-Final Inspection11/30/200111/30/200111/30/2001 12:00:00 AMPPASS
Added by Inspector: 430 On 11/30/2001 1:44:35 PM Fire sprinkler system finaled. OK for perm occ