Inspections for the day of: Wednesday, November 30, 2005.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03507 Final11/30/200511/30/200511/30/2005 4:08:12 PMPPASS
Scheduled by a contractor via Hello! on 11/30/2005 at 7:52:39 AM. Contact: ###-####. ok
ELE05-03297 Final11/29/200511/30/200511/30/2005 3:18:46 PMPPASS
Will be ready for final in the afternoon wednesday.; Phone #: ###-#### Internet Inspection Request from: Steve Syltie ok card signed
ELE05-04302 Rough-In Permanent Service11/30/200511/30/200511/30/2005 2:23:34 PMPFAIL
###-#### cor. met contractor, 300.10 needs bond bushing for RE washers, 310.15 derate wires in emt,250.104 bond hot and cold, 110.12 seal KOs, 358.42&314.15(A) use r/t fittings that are listed for wet location,312.5 needs conn for GEC at service, remove GEC from old panel (j box)
ELE05-04303 Permanent Service11/30/200511/30/200511/30/2005 12:34:44 PMPCANC
Scheduled by a contractor via Hello! on 11/30/2005 at 8:58:39 AM. Contact: ###-####. see added t/s , this is a t/s not p/s
ELE04-03054 Electrical Rough-In11/29/200511/30/200511/30/2005 11:36:30 AMAPASS
REINSPECT POOL BONDING PLEASE; Phone #: ###-#### Internet Inspection Request from: Barry Kendall equipopential grid ok
ELE05-04302 Final11/29/200511/30/200511/30/2005 10:23:30 AMANH
###-#### - twin city no access called and this is a r/i/p/s not final contractor will reschedule and call me also needs to check grounding,is u/g water pipe
ELE05-03486 Final11/29/200511/30/200511/30/2005 10:03:00 AMANH
final on kitchen & bath remodel and service upgrade. george cell # ###-#### Internet Inspection Request from: Andy Rose
notice posted called left # page
ELE05-04048 Final11/29/200511/30/200511/30/2005 9:07:49 AMANR
final on swimming pool Internet Inspection Request from: Andy Rose called
ELE05-03286 Final11/29/200511/30/200511/30/2005 8:48:44 AMANH
Phone #: ###-#### Internet Inspection Request from: Joe Thomas notice posted called
ELE05-04293 Electrical Rough-In11/29/200511/30/200511/30/2005 8:20:29 AMAPART
###-#### - jim Note: underground for post line ok
ELE05-04292 Temporary Service11/29/200511/30/200511/30/2005 8:05:48 AMAPASS
###-#### - jim was done on pm#ele05-04153 p/s u/g new ok
ELE05-04303 Temporary Service11/30/200511/30/200511/30/2005 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 11/30/2005 at 8:58:39 AM. Contact: ###-####. t/s o/h new ok