Inspections for the day of: Wednesday, November 30, 2005.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-03916 Final11/29/200511/30/200511/30/2005 4:27:06 PMACANC
ELECTRICIAN TO MEET BOB AT 7:00AM TO GAIN ACCESS TO AREA.; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL see conf.
ELE05-04164 Final11/30/200511/30/200511/30/2005 4:07:00 PMPFAIL
Scheduled by a contractor via Hello! on 11/30/2005 at 7:54:17 AM. Contact: ###-####. 312.5 abrasion protection shall be provided for conductors entering enclosure,250.53(B) gnd electrodes shall be min 6' apart, called contr, left corr notice
ELE05-04232 Electrical Rough-In11/29/200511/30/200511/30/2005 4:04:48 PMPNR
WALL COVER ONLY; Phone #: ###-#### Internet Inspection Request from: Tyler Bowen called contr, open ko, 1 1/4" shall be provided, mc shall be stapled within 12" of box, said to call when ready for ri
ELE05-04286 Temporary Service11/30/200511/30/200511/30/2005 4:02:55 PMPFAIL
###-#### - jean called, left message, left corr notice,312.5 abrasion protection shall be provided for conductors entering enclosure, 110.12(C) there shall be no broken parts, 310.13, wire shall be suitable for direct burial, BCC job id sticker shall be posted
ELE05-04300 Final11/30/200511/30/200511/30/2005 2:51:36 PMPPASS
dwayne ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, said to label disc, ok to final
ELE05-03867 Final11/30/200511/30/200511/30/2005 10:33:29 AMPPASS
chris --call 1st before insp for access; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie called contr, left survey,352.30(A) rnc shall be strapped within 3' of panel, 440.22(C) a/c brkr shall be max 25A, ok to final
ELE05-04226 Final11/28/200511/30/200511/30/2005 10:02:25 AMAPASS
FINAL INSPECTION, INSTALLED NEW ELECTRICAL SERVICE ON HOME AND RECONNECT TO EXISTING PANEL. ADD A/C CIRCUIT COMPLETE W/GFI, FOR COMPLETE INSTALLATION. HOMEOWNER IS MARION @ 376.5816. THANK YOU; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH called contr to lower panel 1 1/2 " min, and to add gnd rod, ok to final
ELE05-04250 Temporary Service11/29/200511/30/200511/30/2005 9:19:29 AMAFAIL
chris; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, corr not made,
ELE05-04248 Temporary Service11/29/200511/30/200511/30/2005 9:18:54 AMAFAIL
chris; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, corr not made
ELE05-04249 Temporary Service11/29/200511/30/200511/30/2005 9:18:18 AMAPASS
chris; Phone #: ###-#### Internet Inspection Request from: Barbara Moore corr made, t/s u/g n ok
ELE05-03392 Final11/29/200511/30/200511/30/2005 9:00:13 AMAPART
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, need to see bath gfci rev polarity dw wired, sws mtd in kitchen in 101, 102 mt sws, 201 mt sws, 202 locked out, need to inspect unit, strap riser at service.
ELE05-03540 Final11/29/200511/30/200511/30/2005 8:57:12 AMAPART
ron; Phone #: ###-#### Internet Inspection Request from: Barbara Moore called contr, need to look at 201 sw and recpt plates shall be flush,rear gfci loose, 202 sws recpt not mounted in kitchen, hall and dr lites riser shall be strapped
ELE05-03916 Conference11/30/200511/30/200511/30/2005 12:00:00 AMPDONE
ELECTRICIAN TO MEET BOB AT 7:00AM TO GAIN ACCESS TO AREA.; Phone #: ###-#### Internet Inspection Request from: JENNY EMEL met elect and talked about 450.13(B) 75 kva xfmr shall be readily accessible, not in ceiling, type st cord with #2 conductors shall not be used due to ampacity per 400.5(A). 400.8(1) shall not use cord as substitute for fixed wiring of structure.517.78 shall apply for grounding requirements. 517.13 shall apply to redundant grounding. 250.118 shall apply for equipment grounding. Listed equipment shall show requirements for ampacity due to discrepancy of transformer size, equipment load requirements and material supplied with equipment. Will cancel final inspection request until information is obtained.