BLD05-02498
| FIRE-Conference | 11/30/2005 | 11/30/2005 | 12/2/2005 9:54:32 AM | P | DONE |
|
|
Discussed exit signage, emergency lighting, and pocket door hardware requirements on site.
|
BLD05-01384
| FIRE-Final Inspection | 11/30/2005 | 11/30/2005 | 12/1/2005 2:59:37 PM | P | PASS |
|
|
Per inspection and phone call by structural inspector Tony Young, life safety is acceptable.
|
FIR05-00674
| INSP-Final Inspection | 11/30/2005 | 11/30/2005 | 12/1/2005 1:50:43 PM | P | PASS |
|
|
c/n items are complete, fire sprinkler passed inspection.
|
BLD04-03016
| FIRE-Final Inspection | 11/29/2005 | 11/30/2005 | 12/1/2005 10:58:41 AM | P | PASS |
|
|
Life safety passed inspection.
|
BLD04-02999
| FIRE-Final Inspection | 11/29/2005 | 11/30/2005 | 12/1/2005 10:58:02 AM | P | PASS |
|
|
Life safety passed inspection.
|
BLD05-02852
| FIRE-Final Inspection | 11/29/2005 | 11/30/2005 | 12/1/2005 7:50:01 AM | A | CANC |
|
|
No time for inspection.
|
BLD04-02676
| FIRE-Final Inspection | 11/30/2005 | 11/30/2005 | 11/30/2005 5:16:13 PM | P | PASS |
|
|
Racking installation is acceptable, inspection passed.
|
FIR05-00636
| INSP-Final Inspection | 11/29/2005 | 11/30/2005 | 11/30/2005 4:36:15 PM | A | PASS |
|
|
Missing strobe has been added, fire alarm passed inspection. The shelving partly blocking strobe coverage in the workroom to be removed by Dave Miller GC.
|
FIR05-00786
| INSP-Final Inspection | 11/29/2005 | 11/30/2005 | 11/30/2005 4:32:20 PM | A | FAIL |
|
|
Provide missing retaining strap on beam clamp at arm-over hanger, provide hanger for an unsupported arm-over in the network room.
|
FIR05-00661
| INSP-Final Inspection | 11/29/2005 | 11/30/2005 | 11/30/2005 3:25:13 PM | A | PASS |
|
|
Fire sprinkler passed inspection.
|
FIR05-00577
| INSP-Sprinkler Rough-in/Hydro | 11/29/2005 | 11/30/2005 | 11/30/2005 3:04:01 PM | P | PART |
|
|
Overhead hydrostatic test passed, not all c/n items have been completed at this time.
|
FIR04-00523
| INSP-Final Inspection | 11/29/2005 | 11/30/2005 | 11/30/2005 3:01:17 PM | A | FAIL |
|
|
The gas supply failed to shut down upon activation of the hood suppression system.
|
BLD05-01916
| FIRE-Final Inspection | 11/29/2005 | 11/30/2005 | 11/30/2005 1:05:01 PM | A | CANC |
|
|
Inspection has been rescheduled for 12/1 per conversation with contractor.
|
FIR05-00535
| INSP-Final Inspection | 11/29/2005 | 11/30/2005 | 11/30/2005 1:03:45 PM | A | CANC |
|
|
No time available for this inspection today, to be rescheduled.
|
FIR05-00778
| INSP-Final Inspection | 11/29/2005 | 11/30/2005 | 11/30/2005 12:36:01 PM | P | CANC |
|
|
Inspection to be conducted tomorrow per conversation with contractor.
|
FIR05-00507
| INSP-Sprinkler Rough-in/Hydro | 11/30/2005 | 11/30/2005 | 11/30/2005 12:34:39 PM | P | PART |
|
|
Overhead rough-in is acceptable to cover except two locations where a hanger is overspaced and one head is blocked in the hallway.
|
FIR05-00675
| INSP-Final Inspection | 11/30/2005 | 11/30/2005 | 11/30/2005 12:32:24 PM | A | PART |
|
|
Fire alarm for the TI space tested satisfactory, however the audible notification devices in the common area and TI space are not in congruence.
|
FIR05-00729
| INSP-Sprinkler Rough-in/Hydro | 11/29/2005 | 11/30/2005 | 11/30/2005 10:26:30 AM | A | PART |
|
|
Overhead rough-in is good for cover.
|
FIR05-00643
| INSP-Final Inspection | 11/29/2005 | 11/30/2005 | 11/30/2005 9:35:52 AM | A | FAIL |
|
|
Met contractor at the agreed time, however no access was provided into the building. The doors were locked and no key available, no inspection performed, to be rescheduled.
|
BLD05-01736
| FIRE-Final Inspection | 11/29/2005 | 11/30/2005 | 11/30/2005 9:30:46 AM | A | PASS |
|
|
c/n items have been completed, fire life safety passed inspection.
|
FIR05-00675
| INSP-Final Inspection | 11/29/2005 | 11/30/2005 | 11/30/2005 5:11:57 AM | A | CANC |
|
|
Please call Patrick before arrival Internet Inspection Request from: Rick Jackson Inspection cancelled from web by: Rick Jackson
|
BLD05-02311
| FIRE-Final Inspection | 11/30/2005 | 11/30/2005 | 11/30/2005 12:00:00 AM | P | PASS |
|
|
Fire life safety passed inspection.
|
FIR05-00643
| INSP-Final Inspection | 11/29/2005 | 11/30/2005 | 11/29/2005 3:39:29 PM | A | CANC |
|
|
Duplicate inspection already scheduled.
|
FIR05-00535
| INSP-Sprinkler Rough-in/Hydro | 11/28/2005 | 11/30/2005 | 11/29/2005 8:48:04 AM | A | CANC |
|
|
Forrest, Please call when you can set up a time. Thanks-Jim; Phone #: ###-#### Internet Inspection Request from: James Shilton Inspection cancelled from web by: James Shilton
|