ELE06-03276
| ELE-Aging Inspection | 11/30/2006 | 11/30/2006 | 12/4/2006 3:59:47 PM | | DONE |
|
|
suc
|
ELE06-04162
| Final | 11/30/2006 | 11/30/2006 | 11/30/2006 4:10:14 PM | P | PASS |
|
|
robert ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith corr made, signed occ card, ok to final
|
ELE06-04421
| Rough-In Permanent Service | 11/29/2006 | 11/30/2006 | 11/30/2006 4:01:10 PM | P | PASS |
|
|
zane ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok, NO UNDERGROUND SEEN HOUSE TO GARAGE, p/s u/g n ok
|
ELE06-03460
| Rough-In Permanent Service | 11/30/2006 | 11/30/2006 | 11/30/2006 2:36:02 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 11/30/2006 at 8:20:48 AM. Contact: ###-####. ric ok, p/s u/g n ok
|
ELE06-03137
| Final | 11/30/2006 | 11/30/2006 | 11/30/2006 1:57:44 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called left corr notice, nec 348.30(A) fmc shall be securely fastened within 12" of box (heater in mbr), 406.4(D) recpt faces shall be flush with or project from faceplate, 110.3(B) listed equipment shall be installed per mfgr instructions (tub access), BCC 4-05-33(A)(B) equip shall be listed by a nationally recognized testing lab (heater mbr closet)
|
ELE06-02426
| Final | 11/30/2006 | 11/30/2006 | 11/30/2006 1:24:50 PM | P | PASS |
|
|
Mechanical room will be open for aft. inspection; Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot ok to final, no card to sign, will put on nameplates for equip
|
ELE06-04423
| Electrical Rough-In | 11/29/2006 | 11/30/2006 | 11/30/2006 10:59:24 AM | A | PASS |
|
|
roger ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith ric ok
|
ELE06-03764
| Final | 11/29/2006 | 11/30/2006 | 11/30/2006 10:36:45 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/29/2006 at 4:33:19 PM. Contact: ###-####. ok to final
|
ELE06-04422
| Rough-In Permanent Service | 11/29/2006 | 11/30/2006 | 11/30/2006 10:31:39 AM | A | CANC |
|
|
hz ###-#### see p/s and ri
|
ELE06-04422
| Electrical Rough-In | 11/30/2006 | 11/30/2006 | 11/30/2006 10:31:09 AM | A | PART |
|
|
hz ###-#### ric except jetted tub ok, left corr notice, BCC4-05-33(A)(B) all equipment shall be listed by a nationlly recognized testing lab-jetted tub
|
ELE06-04422
| Permanent Service | 11/30/2006 | 11/30/2006 | 11/30/2006 10:29:11 AM | A | PASS |
|
|
hz ###-#### p/s u/g n ok
|
ELE06-03763
| Final | 11/29/2006 | 11/30/2006 | 11/30/2006 9:52:58 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 11/29/2006 at 4:32:29 PM. Contact: ###-####. called , left message, told to chg a/c bkr from 50a to max 45a per nameplate, check recpt faceplates for flush against wall, ok to final
|
ELE06-04291
| Permanent Service | 11/29/2006 | 11/30/2006 | 11/30/2006 9:08:21 AM | A | CANC |
|
|
bud - space 9 ; Phone #: ###-#### Internet Inspection Request from: Patricia Smith talked to contr, said to be sure trailer at site, and put space numbers on each permit in order to turn each one on. This permit has no trailer, just pole with service on it. Also told to number trailer along with service.
|
ELE06-04413
| Permanent Service | 11/29/2006 | 11/30/2006 | 11/30/2006 8:43:09 AM | A | PASS |
|
|
adam; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles told contr to anchor guy kit before power and move metal guard below panel, p/s o/h rec ok
|
ELE06-02426
| Final | 11/29/2006 | 11/30/2006 | 11/30/2006 8:23:41 AM | A | PART |
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called contr to recall, no access to elect room, pole lights ok
|