BLD04-00079
| FIRE-Final Inspection | 11/30/2007 | 11/30/2007 | 12/4/2007 5:12:32 PM | P | FAIL |
|
|
Need to verify functional EM lighting.
|
BLD04-01308
| FIRE-Final Inspection | 11/30/2007 | 11/30/2007 | 12/4/2007 5:11:44 PM | P | FAIL |
|
|
Need to verify functional EM lighting at all three stairways, provide signage at the gates to the basement level in the stariways, remove covering at a fire sprinkler head in the south stairway 1st floor exit discharge.
|
FIR07-00737
| INSP-Sprinkler Rough-in/Hydro | 11/30/2007 | 11/30/2007 | 11/30/2007 2:44:09 PM | P | PART |
|
|
See approved plan set for areas inspected today.
|
FIR07-00913
| INSP-Sprinkler Rough-in/Hydro | 11/30/2007 | 11/30/2007 | 11/30/2007 2:43:18 PM | P | PART |
|
|
Red lined areas on the plan at the basement level okayed for ceiling cover.
|
FIR07-00450
| INSP-Final Inspection | 11/28/2007 | 11/30/2007 | 11/30/2007 2:42:14 PM | A | FAIL |
|
|
Noted several locations in need of av notification adjustment, some devices are missing, incorrect cd settings, blocked or obstructed, red lined areas on plans, discussed inspection scheduling.
|
FIR06-00504
| INSP-Final Inspection | 11/29/2007 | 11/30/2007 | 11/30/2007 12:57:47 PM | A | PART |
|
|
Items on correction notice are complete with the exception of four missing DP heads, need to provide coverage for an open space at the 1st floor or completely enclose as indicated on the building plans to create a non-combustible concealed space, repair the flow switch at the pump discharge manifold, ceiling tiles at some locations are still missing.
|
FIR07-00772
| INSP-Sprinkler Rough-in/Hydro | 11/29/2007 | 11/30/2007 | 11/30/2007 11:57:24 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 11/29/2007 at 5:00:15 PM. Contact: ###-####. Noted two pendent heads at the east side have been changed to QR as discussed. Sprinkler final pending removal of tape at covered uprights and escutcheons at hard lid ceilings when painting and sheetrock patching is completed. Contact phone number is incorrect, line has been disconnected.
|
FIR07-00481
| INSP-Final Inspection | 11/29/2007 | 11/30/2007 | 11/30/2007 11:36:43 AM | A | PASS |
|
|
Sprinkler finaled.KR
|
BLD06-03088
| FIRE-Final Inspection | 11/30/2007 | 11/30/2007 | 11/30/2007 10:43:02 AM | P | PASS |
|
|
Corrections have been verified for compliance, fire life safety finaled.
|
FIR07-00441
| INSP-Final Inspection | 11/29/2007 | 11/30/2007 | 11/30/2007 10:42:05 AM | A | PASS |
|
|
Corrections verified, resubmittals for as-built plans accepted, final inspection passed. NFPA 72 record of completion forms to be delivered to PDS fire office today for signature as agreed.
|
BLD07-02538
| FIRE-Final Inspection | 11/29/2007 | 11/30/2007 | 11/30/2007 9:53:15 AM | A | PASS |
|
|
Fire life safety is acceptable per scope of work, noted missing hardware at the door to the display room to be verified for code compliance at structural final.
|
BLD06-03088
| FIRE-Final Inspection | 11/30/2007 | 11/30/2007 | 11/30/2007 9:51:58 AM | A | PEND |
|
|
|
FIR07-00845
| INSP-Final Inspection | 11/29/2007 | 11/30/2007 | 11/30/2007 9:48:46 AM | A | PASS |
|
|
Fire sprinkler final inspection passed, permit finaled.
|
BLD07-01605
| FIRE-Final Inspection | 11/29/2007 | 11/30/2007 | 11/30/2007 9:24:48 AM | A | FAIL |
|
|
Need to remove one sprinkler head were a wall was taken down. to close to another head .head is not required for coverage.KR
|
FIR07-00471
| FIR-Aging Inspection | 11/30/2007 | 11/30/2007 | 11/30/2007 8:57:14 AM | | DEFR |
|
|
wip
|