Inspections for the day of: Friday, November 30, 2007.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00825 INSP-Sprinkler Rough-in11/30/200711/30/200712/3/2007 7:49:12 AMPCANC
OH Cover inspection
Phone #: ###-#### x1234 Internet Inspection Request from: Alicia Pauley
FIR07-00866 INSP-Final Inspection11/29/200711/30/200711/30/2007 3:46:33 PMPCANC
mike Phone #: ###-####
FIR07-00761 INSP-Final Inspection11/30/200711/30/200711/30/2007 3:44:42 PMPFAIL
The project is not ready to final yet. The sprinklers in the curved ceiling are ok to cover and the kitchen area is ok to cover.
BLD06-03595 FIRE-Final Inspection11/30/200711/30/200711/30/2007 3:41:23 PMPPASS
life safety passed.
BLD05-01656 FIRE-Final Inspection11/29/200711/30/200711/30/2007 2:31:40 PMAFAIL
Fire hydrants are less than 40 feet from building, Let contractor know that he needs to call Dave Hanneman for approval. Also missing sign at north entrance designating fire lanes.Missing fire review notes on approved set of plans they were not on site.KR
BLD07-01712 FIRE-Final Inspection11/29/200711/30/200711/30/2007 2:27:20 PMAFAIL
Cannot final until shell is final.extinguisher is tagged and hanging.
FIR06-00367 INSP-Final Inspection11/29/200711/30/200711/30/2007 1:24:46 PMAPASS
Permit finaled. The slave dialer has the required 24 hour battery backup.
FIR07-00274 INSP-Final Inspection11/28/200711/30/200711/30/2007 12:17:32 PMAPASS
permit finaled
FIR07-00637 INSP-Sprinkler Rough-in/Hydro11/28/200711/30/200711/30/2007 12:04:06 PMAPART
The hydro test for the first floor passed. This does not include either of the canopies. I stopped the rough-in inspection for the first floor due to wire still being attached to the sprinkler piping, lose hangers, missing hangers, earthquake bracing not being installed and no patching of the fire proofing has been done yet. Also the sprinkler plans will need to be resubmitted to show the changes which include the deletion of the PIV.
BLD06-03598 FIRE-Final Inspection11/29/200711/30/200711/30/2007 10:15:36 AMAPASS
life safety passed.
FIR07-00517 INSP-Final Inspection11/29/200711/30/200711/30/2007 9:13:21 AMAPASS
permit finaled. The light fixtures have been changed to can lights which no longer are obstructions.
FIR07-00637 INSP-Sprinkler Rough-in/Hydro11/28/200711/30/200711/28/2007 4:20:56 PMACANC
Leroy is the contact. Thanks Phone #: ###-#### Internet Inspection Request from: Stan Beus Inspection cancelled from web by: Stan Beus