FIR12-00593
| INSP-Final Inspection | 11/29/2012 | 11/30/2012 | 11/30/2012 3:51:23 PM | A | PASS |
|
|
Permit finaled
|
FIR12-00628
| INSP-Sprinkler Rough-in | 11/30/2012 | 11/30/2012 | 11/30/2012 3:34:13 PM | P | PASS |
|
|
Could not find approved plans on site. Walls have been installed and the upright sprinkler protection appears to be correct. The two branchlines that were located too close to one another have been modified to increase spacing between the two lines. Painters had many of the heads covered so their removal will need to be verified at the final. Per the project history plans still have not been resubmitted for review and the hydro test is still needed. I left message on Stephen's cell phone to call me back.
|
FIR12-00687
| INSP-Final Inspection | 11/29/2012 | 11/30/2012 | 11/30/2012 3:21:45 PM | P | PASS |
|
|
Newly modified hood suppression functioned correctly. No alarm point was changed.
|
FIR12-00680
| INSP-Sprinkler Rough-in | 11/30/2012 | 11/30/2012 | 11/30/2012 2:13:56 PM | P | PASS |
|
|
Underground supply line cover inspection passed. Piping can be covered.
|
FIR11-00431
| INSP-Final Inspection | 11/30/2012 | 11/30/2012 | 11/30/2012 1:40:13 PM | P | CANC |
|
|
Per james and I's discussion this inspection will be rescheduled for monday. Phone #: ###-####
|
FIR12-00423
| INSP-Sprinkler Rough-in | 11/29/2012 | 11/30/2012 | 11/30/2012 11:54:45 AM | A | PASS |
|
|
The first floor breeze-way piping can be covered. The heat tape/insulation has been installed.
|
FIR12-00471
| INSP-Final Inspection | 11/29/2012 | 11/30/2012 | 11/30/2012 10:16:29 AM | A | PASS |
|
|
Permit finaled. Underground flush passed as well. The outside alarm bell is ok t obe silenced by the fire/burg. panel since the internal smoke alarms do have sounder bases.
|
FIR12-00638
| INSP-Sprinkler Rough-in | 11/29/2012 | 11/30/2012 | 11/30/2012 9:38:08 AM | A | PART |
|
|
The sprinkler piping can not be covered due to the tenting not being adequate in many locations. However the underground supply piping can now be buried.
|