Inspections for the day of: Monday, November 30, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorAlan Hauser
TitleMEC-COM/RES INSPECTOR
Phone #794-9453
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC15-05589 Final11/30/201511/30/201511/30/2015 4:13:31 PMPPASS
MEC15-05592 Final11/30/201511/30/201511/30/2015 3:02:00 PMPFAIL
need 1" clearance around oval b-vent in wall, replace duct that is only inner liner of flex with listed air connector product and upper and lower combustion air openings into furnace room.
MEC15-05551 Final11/30/201511/30/201511/30/2015 2:39:57 PMPPASS
MEC15-05609 Final11/30/201511/30/201511/30/2015 2:00:49 PMPPASS
MEC15-05590 Pressure Test11/30/201511/30/201511/30/2015 11:24:50 AMPPART
PHASE 1
17 flue test ok, and 11 dryer ducts ok. dryers are supplied by tenants and commom laundry room dryers supplied by owner. all dryers will be tagged as length and how many 90's.
MEC15-05475 Final11/25/201511/30/201511/30/2015 10:31:07 AMAPASS
MEC15-05475 Pressure Test11/25/201511/30/201511/30/2015 10:30:03 AMAPASS
20#
MEC15-02941 Final11/25/201511/30/201511/30/2015 10:17:21 AMPFAIL
All duct in garage needs to be r-8 insulation (no insulation at this time in duct) and need proper filter access and proper filter that fits duct size. filter now has been cut down and bowed to fit into opening of furnace.
MEC15-01039 Mec-Aging Inspection11/30/201511/30/201511/30/2015 9:03:02 AM PASS
MEC15-01039 DOC - Permit Expired11/30/201511/30/201511/30/2015 9:02:44 AMPPASS
MEC15-05593 Pressure Test11/25/201511/30/201511/30/2015 8:32:44 AMACANC
Phone #: ###-#### >> Inspection requested via web by Joe Bertwell Inspection cancelled from web by: Joe Bertwell
MEC15-05593 Final11/25/201511/30/201511/30/2015 8:32:40 AMACANC
Phone #: ###-#### >> Inspection requested via web by Joe Bertwell Inspection cancelled from web by: Joe Bertwell