Inspections for the day of: Wednesday, November 30, 2016.
Number of inspections: 5
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE16-01946 Electrical Rough-In11/29/201611/30/201611/30/2016 2:09:06 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Basement walls added after gear installed. Rough in ok cover
ELE16-01946 Permanent Service11/29/201611/30/201611/30/2016 1:45:29 PMPFAIL
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
110.24- Available fault current shall be posted prior to permanent service inspection.
ELE16-03736 Conference11/29/201611/30/201611/30/2016 12:44:44 PMADONE
brandon Phone #: ###-####
Discussed what is electrically needed. GFCI protect ungrounded circuits with grounding type receptacles installed, AFCI protect remodelled bedroom, make sure all abandoned wiring is disconnected, check wiring that was pre-installed in bed. Check for dedicated 20amp bath.
ELE16-01667 Electrical Rough-In11/29/201611/30/201611/30/2016 10:20:41 AMAPASS
Four drop ceilings Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty
Units 401, 402, 403, 404 drop ceilings rough in ok cover
ELE16-02587 Permanent Service11/29/201611/30/201611/30/2016 9:02:48 AMAPASS
Phone #: ###-#### Inspection requested via web by PAUL PINNEY
Main breaker AIC rated 25K with 27K line to ground, 25K Line to Line listed on print. Asked contractor to call Idaho Power for actual rating. Will approve for heat so water lines don't freeze. Must verfy and post for final. p/s u/g n ok