ELE16-01946
| Electrical Rough-In | 11/29/2016 | 11/30/2016 | 11/30/2016 2:09:06 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Basement walls added after gear installed. Rough in ok cover
|
ELE16-01946
| Permanent Service | 11/29/2016 | 11/30/2016 | 11/30/2016 1:45:29 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 110.24- Available fault current shall be posted prior to permanent service inspection.
|
ELE16-03736
| Conference | 11/29/2016 | 11/30/2016 | 11/30/2016 12:44:44 PM | A | DONE |
|
|
brandon Phone #: ###-#### Discussed what is electrically needed. GFCI protect ungrounded circuits with grounding type receptacles installed, AFCI protect remodelled bedroom, make sure all abandoned wiring is disconnected, check wiring that was pre-installed in bed. Check for dedicated 20amp bath.
|
ELE16-01667
| Electrical Rough-In | 11/29/2016 | 11/30/2016 | 11/30/2016 10:20:41 AM | A | PASS |
|
|
Four drop ceilings Call Craig Phone #: ###-#### Inspection requested via web by Tom Betty Units 401, 402, 403, 404 drop ceilings rough in ok cover
|
ELE16-02587
| Permanent Service | 11/29/2016 | 11/30/2016 | 11/30/2016 9:02:48 AM | A | PASS |
|
|