Inspections for the day of: Wednesday, November 30, 2016.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00540 INSP-Final Inspection11/30/201611/30/201611/30/2016 3:22:01 PMPPART
A temporary for the fire sprinkler permit is ok until the new, shorter, wall PIV has been installed and tested. Supposed arrival date for the new PIV is 12-7-16
FIR16-00644 INSP-Sprinkler Rough-in11/30/201611/30/201611/30/2016 3:20:48 PMPPASS
Piping above the hardlid next to the elevator as marked on the plans is ok to cover.
FIR16-00364 INSP-Final Inspection11/29/201611/30/201611/30/2016 2:52:18 PMPCANC
The as-build plans for this building have not been submitted and approved yet.
BLD16-03673 FIRE-Final Inspection11/30/201611/30/201611/30/2016 2:51:46 PMPFAIL
No city approved plans on site. No inspection performed.
BLD16-03759 FIRE-Final Inspection11/29/201611/30/201611/30/2016 1:31:47 PMAPASS
Life safety passed. I noted a audible sync problem with the fire alarm system. As per Assistant Chief Ron this issue will need addressed prior to the next remodel.
FIR16-00720 INSP-Final Inspection11/29/201611/30/201611/30/2016 1:31:01 PMAPASS
Permit finaled. I noted a audible sync problem. As per Assistant Chief Ron this issue will need addressed prior to the next remodel.
BLD16-04265 FIRE-Final Inspection11/29/201611/30/201611/30/2016 12:12:11 PMAFAIL
Repair the emergency lights, provide double door exiting with correct hardware out of the back door as per plans or get plan review approval for single door exiting, provide annual inspection for the basement fire sprinkler system, provide three fire extinguishers upstairs and another three down stairs.
FIR16-00031 INSP-Sprinkler Rough-in/Hydro11/29/201611/30/201611/30/2016 11:29:48 AMPCANC
Mark Jensen is the contact for this inspection. He needs a rough in to cover inspection on the west system. Thank you. Phone #: ###-#### Inspection requested via web by Stan Beus
BLD16-02213 FIRE-Final Inspection11/29/201611/30/201611/30/2016 11:16:38 AMAPASS
Life safety passed. A baffle has been provided
BLD16-01452 FIRE-Final Inspection11/29/201611/30/201611/30/2016 10:33:33 AMAFAIL
Provide final inspections for the project related fire alarm and fire sprinkler permits, Provide occupant load sign and provide clearance at the FDC of 36" as discussed and as directed by the fire dept.
FIR16-00540 INSP-Sprinkler Rough-in/Hydro11/30/201611/30/201611/30/2016 10:31:05 AMPPASS
Overhead hydro test passed. Rough-in for the two new pendants passed. Piping can be covered.
FIR16-00651 INSP-Final Inspection11/29/201611/30/201611/30/2016 10:29:42 AMAFAIL
Contact plan review to see if as-builts or plan modifications are required for the new strobe and changes in the candellas of the other strobes, provide strobe coverage in the rear exit area, provide immediate shut down of the hvac units per the IMC, provide record of completion forms.
BLD16-03748 FIRE-Final Inspection11/29/201611/30/201611/30/2016 10:25:57 AMACANC
No life safety sign off required. I contacted owner to reschedule.

Phone #: ###-#### Inspection requested via web by Shannon Wall
FIR16-00649 INSP-Final Inspection11/29/201611/30/201611/30/2016 8:18:46 AMAPASS
permit finaled