Inspections for the day of: Thursday, November 30, 2017.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE17-03734 Electrical Rough-In11/30/201711/30/201711/30/2017 2:41:35 PMPPASS
We are requesting a rough-in inspection walls and ceiling for this afternoon. Our contact is Luke ###-####. Thank you. Phone #: ###-#### Inspection requested via web by Clint Tate
Prep room A homerun cove only rough in ok cover
ELE17-03878 Conference11/30/201711/30/201711/30/2017 2:41:02 PMPDONE
Received text from kevin at ###-#### asking if #4/0 SER is ok to use to feed 200 amp panel in garage off 200 amp meter main with 8 to 16 spaces. The 200 amp service will serve all of the load associated with entire residence as per 310.15(B)(7) so #4/0 SER OK to use. Called contact and left message.
ELE17-04027 Conference11/30/201711/30/201711/30/2017 1:43:46 PMPDONE
Call 1 hour prior to confirm Phone #: ###-#### Inspection requested via web by Steve Craig
Discussed if boxes permitted above decorative drop partial ceiling. Wood panels will be small and removeable, box access ok above. Also showroom window receptacles may be few inches over 18" due to structural steel beam. OK. Asked about required emergency and egress lighting informed all depends on occupancy load and to check with life/safety inspector.
ELE17-00864 Final11/29/201711/30/201711/30/2017 11:36:18 AMAPASS
Sign electrical final. Contact Corey Welch with questions. Phone #: ###-#### Inspection requested via web by Tom Noeker Final ok
ELE17-02830 Final11/29/201711/30/201711/30/2017 11:35:51 AMAPASS
Sign electrical final. Contact Corey Welch with questions. Phone #: ###-#### Inspection requested via web by Tom Noeker Final ok
ELE17-00864 Electrical Rough-In11/30/201711/30/201711/30/2017 11:35:37 AMPPASS
Sign electrical final. Contact Corey Welch with questions. Phone #: ###-#### Inspection requested via web by Tom Noeker
Listing and disconnecting means confirmed rough in ok
ELE17-02830 Electrical Rough-In11/30/201711/30/201711/30/2017 11:34:48 AMPPASS
Sign electrical final. Contact Corey Welch with questions. Phone #: ###-#### Inspection requested via web by Tom Noeker
Listing and disconnecting confirmed. Rough in ok
ELE17-04029 Final11/29/201711/30/201711/30/2017 10:57:06 AMPPASS
call for access, ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER Final ok
ELE17-04029 Electrical Rough-In11/29/201711/30/201711/30/2017 10:56:35 AMPPASS
call for access, ###-#### Phone #: ###-#### Inspection requested via web by PAT MILLER
Misc receptacles in several offices. Rough in ok cover
ELE17-03112 Final11/27/201711/30/201711/30/2017 10:20:24 AMAFAIL
Phone #: ###-#### Inspection requested via web by steve ragan
110.3- Devices shall be wired as per instructions. Reverse polarity GFCI in break room.
406.6- All receptacles shall have faceplates installed. Break room and IT/storage room 2 gang.
ELE17-03112 Electrical Rough-In11/30/201711/30/201711/30/2017 10:20:14 AMPPASS
Phone #: ###-#### Inspection requested via web by steve ragan
Grid rough in ok cover
ELE17-02726 Final11/29/201711/30/201711/30/2017 9:34:05 AMAPASS
Code 2010 Phone #: ###-#### Inspection requested via web by danny perrine Final ok
ELE17-03981 Rough-In Permanent Service11/30/201711/30/201711/30/2017 8:34:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Bob Glenn
Rough in ok cover p/s u/g n ok