MEC17-03806
| Rough-in | 11/30/2017 | 11/30/2017 | 12/1/2017 10:41:14 AM | P | PASS |
|
|
Field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney- R/I ok
|
MEC17-05337
| Pressure Test | 11/30/2017 | 11/30/2017 | 11/30/2017 4:04:02 PM | P | PART |
|
|
20lb gas pass- need flue test witnessed
|
MEC17-05317
| Final | 11/30/2017 | 11/30/2017 | 11/30/2017 3:46:59 PM | P | PASS |
|
|
|
MEC17-00179
| Final | 11/30/2017 | 11/30/2017 | 11/30/2017 3:19:32 PM | P | CANC |
|
|
Phone #: ###-#### Inspection requested via web by Marisa Hone- per phone call with homeowner rescheduled for tomorrow PM
|
MEC17-05389
| Final | 11/29/2017 | 11/30/2017 | 11/30/2017 2:56:55 PM | P | PASS |
|
|
PLEASE CALL OUR LEAD INSTALLER DAKODA WHEN 30 MINS IN ROUTE Phone #: ###-#### Inspection requested via web by Rick Montgomery
|
MEC17-02803
| Final | 11/28/2017 | 11/30/2017 | 11/30/2017 2:44:05 PM | P | PASS |
|
|
Please call Glenn Reinhart at ###-#### prior to inspection Phone #: ###-#### Inspection requested via web by Mary LaFayette
|
MEC17-03806
| Pressure Test | 11/30/2017 | 11/30/2017 | 11/30/2017 2:25:21 PM | P | FAIL |
|
|
Field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney- 60lb gas fail gauge stuck- 20lb gas pass- 5lb flue pass
|
MEC17-05217
| Final | 11/29/2017 | 11/30/2017 | 11/30/2017 1:57:45 PM | P | PASS |
|
|
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 1:30 PM . Contact for Right Now is Mary ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
|
MEC17-05217
| Pressure Test | 11/30/2017 | 11/30/2017 | 11/30/2017 1:57:30 PM | P | PASS |
|
|
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 1:30 PM . Contact for Right Now is Mary ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- 5lb flue pass
|
MEC17-05264
| Rough-in | 11/30/2017 | 11/30/2017 | 11/30/2017 1:25:36 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kathryn Martin- R/I ok- need to add dryer exhaust to permit and pay fee-
|
MEC17-05353
| Final | 11/30/2017 | 11/30/2017 | 11/30/2017 1:14:55 PM | P | CANC |
|
|
wrong address from chads text
|
MEC17-05335
| Pressure Test | 11/30/2017 | 11/30/2017 | 11/30/2017 1:10:15 PM | P | PASS |
|
|
please call Chuck ###-#### Phone #: ###-#### Inspection requested via web by Krista Boss- 20lb gas pass- need to add other to permit and pay fee- need air balance and duct blast reports onsite at final
|
MEC17-04861
| Final | 11/29/2017 | 11/30/2017 | 11/30/2017 11:45:42 AM | A | PASS |
|
|
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 11:30 AM . Contact for Right Now is Mary ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette
|
MEC17-04861
| Pressure Test | 11/30/2017 | 11/30/2017 | 11/30/2017 11:45:25 AM | P | PASS |
|
|
This is a Flue Pressure and Final Inspect. Please meet our installer at home at 11:30 AM . Contact for Right Now is Mary ###-#### Phone #: ###-#### Inspection requested via web by Mary LaFayette- 5lb flue pass
|
MEC17-05337
| Pressure Test | 11/30/2017 | 11/30/2017 | 11/30/2017 10:54:15 AM | A | NR |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette- gas pressure leaking- need to add other to permit and pay fee for duct work being installed in house- need air balance and duct blast reports by final inspection- talked with Mary about this
|
MEC17-04892
| Rough-in | 11/29/2017 | 11/30/2017 | 11/30/2017 10:18:45 AM | A | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Bryan Palmer- need approved prints onsite for inspection- need auxiliary drain pan installed per 307.2.3 IMC- need to insulate filter box excluding access door- reinspection needed
|
MEC17-03257
| Final | 11/29/2017 | 11/30/2017 | 11/30/2017 9:59:31 AM | A | PASS |
|
|
mechanical fireplace final inspection Phone #: ###-#### Inspection requested via web by Dan Otero
|
MEC17-05375
| Final | 11/29/2017 | 11/30/2017 | 11/30/2017 9:41:52 AM | A | PASS |
|
|
please call homeowner for access Phone #: ###-#### Inspection requested via web by Aaron Alandt
|
MEC17-05221
| Pressure Test | 11/30/2017 | 11/30/2017 | 11/30/2017 9:32:16 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by MICHAEL BYERS- 20lb gas pass whle system- gas piping on roof needs secured to hanger on roof by final
|
MEC17-05187
| Rough-in | 11/29/2017 | 11/30/2017 | 11/30/2017 9:31:41 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Steve Torgerson- seal on duct ok- insulation ok- ok to cover hard lids for restrooms- need to check on smoke detectors and economizers and have install by final
|
MEC17-01368
| Mec-Aging Inspection | 11/30/2017 | 11/30/2017 | 11/30/2017 8:39:30 AM | | FAIL |
|
|
no final called in
|