Inspections for the day of: Thursday, November 30, 2017.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD16-04564 FIRE-Final Inspection11/30/201711/30/201711/30/2017 2:59:37 PMPPASS
Life safety passed

Cory Phone #: ###-####
FIR17-00693 INSP-Final Inspection11/29/201711/30/201711/30/2017 2:18:33 PMPFAIL
No plans or small documents on site, Manual pull is too close to hood and mounted too high, suppression system did not discharge when test link was cut.

Nate Phone #: ###-####
FIR17-00667 INSP-Final Inspection11/30/201711/30/201711/30/2017 2:17:22 PMPFAIL
Not ready for final yet. No testing performed. Contractor to contact the plan reviewer about wether plan modifications are needed or as-builts due to the additional devices, deleted devices, changed devices. Floor plan does not match. No small documents were on site and the approved plans are so small I can hardly read them.

Paula-would like as late as possible Phone #: ###-####
FIR17-00431 INSP-Final Inspection11/29/201711/30/201711/30/2017 1:38:16 PMPFAIL
Missing all small documents, communication does not match plans, appears atleast two strobes need to be added. No testing performed.
FIR17-00571 INSP-Final Inspection11/29/201711/30/201711/30/2017 1:37:05 PMPFAIL
Electrical problems. No testing performed.

Dave Phone #: ###-####
FIR17-00682 INSP-Sprinkler Rough-in11/30/201711/30/201711/30/2017 10:46:37 AMAPASS
See the city approved plans for location with todays date where piping is ok to cover.
FIR17-00632 INSP-Sprinkler Rough-in11/29/201711/30/201711/30/2017 10:07:04 AMAPASS
Underground supply piping is ok for cover.
FIR17-00499 INSP-Sprinkler Rough-in11/29/201711/30/201711/30/2017 8:32:52 AMAPASS
The sprinkler piping in the new OR room is ok to cover.
FIR17-00670 INSP-Sprinkler Rough-in11/29/201711/30/201711/29/2017 4:27:16 PMACANC
Bryan Collins is the contact for this Underground Rough-in. Thank you for your time. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR17-00640 INSP-Final Inspection11/27/201711/30/201711/27/2017 8:59:02 PMACANC
Please call Jake before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello