BLD16-04564
| FIRE-Final Inspection | 11/30/2017 | 11/30/2017 | 11/30/2017 2:59:37 PM | P | PASS |
|
|
Life safety passed
Cory Phone #: ###-####
|
FIR17-00693
| INSP-Final Inspection | 11/29/2017 | 11/30/2017 | 11/30/2017 2:18:33 PM | P | FAIL |
|
|
No plans or small documents on site, Manual pull is too close to hood and mounted too high, suppression system did not discharge when test link was cut.
Nate Phone #: ###-####
|
FIR17-00667
| INSP-Final Inspection | 11/30/2017 | 11/30/2017 | 11/30/2017 2:17:22 PM | P | FAIL |
|
|
Not ready for final yet. No testing performed. Contractor to contact the plan reviewer about wether plan modifications are needed or as-builts due to the additional devices, deleted devices, changed devices. Floor plan does not match. No small documents were on site and the approved plans are so small I can hardly read them.
Paula-would like as late as possible Phone #: ###-####
|
FIR17-00431
| INSP-Final Inspection | 11/29/2017 | 11/30/2017 | 11/30/2017 1:38:16 PM | P | FAIL |
|
|
Missing all small documents, communication does not match plans, appears atleast two strobes need to be added. No testing performed.
|
FIR17-00571
| INSP-Final Inspection | 11/29/2017 | 11/30/2017 | 11/30/2017 1:37:05 PM | P | FAIL |
|
|
Electrical problems. No testing performed.
Dave Phone #: ###-####
|
FIR17-00682
| INSP-Sprinkler Rough-in | 11/30/2017 | 11/30/2017 | 11/30/2017 10:46:37 AM | A | PASS |
|
|
See the city approved plans for location with todays date where piping is ok to cover.
|
FIR17-00632
| INSP-Sprinkler Rough-in | 11/29/2017 | 11/30/2017 | 11/30/2017 10:07:04 AM | A | PASS |
|
|
Underground supply piping is ok for cover.
|
FIR17-00499
| INSP-Sprinkler Rough-in | 11/29/2017 | 11/30/2017 | 11/30/2017 8:32:52 AM | A | PASS |
|
|
The sprinkler piping in the new OR room is ok to cover.
|
FIR17-00670
| INSP-Sprinkler Rough-in | 11/29/2017 | 11/30/2017 | 11/29/2017 4:27:16 PM | A | CANC |
|
|
Bryan Collins is the contact for this Underground Rough-in. Thank you for your time. Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
|
FIR17-00640
| INSP-Final Inspection | 11/27/2017 | 11/30/2017 | 11/27/2017 8:59:02 PM | A | CANC |
|
|
Please call Jake before heading out, thanks! Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|