Inspections for the day of: Thursday, November 30, 2017.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR17-00601 INSP-Final Inspection11/29/201711/30/201711/30/2017 5:22:45 PMPFAIL
HVAC units did not shut down during in duct detector activation.
BLD17-03356 FIRE-Final Inspection11/30/201711/30/201711/30/2017 1:57:02 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work passed/complete.
BLD17-03293 FIRE-Final Inspection11/30/201711/30/201711/30/2017 1:56:44 PMPPASS
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work passed/complete.
FIR17-00234 INSP-Alarm Testing11/28/201711/30/201711/30/2017 12:18:40 PMAFAIL
Smoke curtians did not drop when associated smoke detector was activated. Install does not match city approved drawings, contractor needs to resubmit as-built drawings. Levels 1, 2, 3 and 4 are missing audio visual devices, audio visual devices in parking garage are overspaced. FDC bell did not activate with dry system trip.
BLD16-01059 FIRE-Final Inspection11/30/201711/30/201711/30/2017 12:01:42 PMAFAIL
Need 18 inches of clearance from bottom of fire sprinkler deflector to top of storage (closets and pantries are the main issue). No exterior signage for roof access or fire sprinkler riser room. Provide emergency lighting for exit discharge landings. FIR permits for both fire sprinkler and fire alarm need to be finaled before life fire safety inspection can be completed.
FIR17-00267 INSP-Sprinkler Rough-in11/29/201711/30/201711/30/2017 11:24:47 AMAPART
Rough to cover inspection for level 3 west side complete, level 3 west side approved for cover.
BLD17-03697 FIRE-Final Inspection11/30/201711/30/201711/30/2017 11:21:18 AMAPASS
Fire sprinkler inspection complete, life fire safety inspection for area of work passed/complete.
BLD13-01349 FIRE-Final Inspection11/29/201711/30/201711/30/2017 10:40:28 AMACANC
Wrong permit scheduled.
FIR17-00679 INSP-Sprinkler Rough-in11/29/201711/30/201711/29/2017 3:20:24 PMAPART
Underground supply inspected for cover from the in building riser to the spot for tie-in, area inspected approved for cover. Remaining pipe for the tie-in will be scheduled for a later date.