FIR17-00601
| INSP-Final Inspection | 11/29/2017 | 11/30/2017 | 11/30/2017 5:22:45 PM | P | FAIL |
|
|
HVAC units did not shut down during in duct detector activation.
|
BLD17-03356
| FIRE-Final Inspection | 11/30/2017 | 11/30/2017 | 11/30/2017 1:57:02 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work passed/complete.
|
BLD17-03293
| FIRE-Final Inspection | 11/30/2017 | 11/30/2017 | 11/30/2017 1:56:44 PM | P | PASS |
|
|
No fire sprinkler modifications, no fire alarm modifications, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for area of work passed/complete.
|
FIR17-00234
| INSP-Alarm Testing | 11/28/2017 | 11/30/2017 | 11/30/2017 12:18:40 PM | A | FAIL |
|
|
Smoke curtians did not drop when associated smoke detector was activated. Install does not match city approved drawings, contractor needs to resubmit as-built drawings. Levels 1, 2, 3 and 4 are missing audio visual devices, audio visual devices in parking garage are overspaced. FDC bell did not activate with dry system trip.
|
BLD16-01059
| FIRE-Final Inspection | 11/30/2017 | 11/30/2017 | 11/30/2017 12:01:42 PM | A | FAIL |
|
|
Need 18 inches of clearance from bottom of fire sprinkler deflector to top of storage (closets and pantries are the main issue). No exterior signage for roof access or fire sprinkler riser room. Provide emergency lighting for exit discharge landings. FIR permits for both fire sprinkler and fire alarm need to be finaled before life fire safety inspection can be completed.
|
FIR17-00267
| INSP-Sprinkler Rough-in | 11/29/2017 | 11/30/2017 | 11/30/2017 11:24:47 AM | A | PART |
|
|
Rough to cover inspection for level 3 west side complete, level 3 west side approved for cover.
|
BLD17-03697
| FIRE-Final Inspection | 11/30/2017 | 11/30/2017 | 11/30/2017 11:21:18 AM | A | PASS |
|
|
Fire sprinkler inspection complete, life fire safety inspection for area of work passed/complete.
|
BLD13-01349
| FIRE-Final Inspection | 11/29/2017 | 11/30/2017 | 11/30/2017 10:40:28 AM | A | CANC |
|
|
Wrong permit scheduled.
|
FIR17-00679
| INSP-Sprinkler Rough-in | 11/29/2017 | 11/30/2017 | 11/29/2017 3:20:24 PM | A | PART |
|
|
Underground supply inspected for cover from the in building riser to the spot for tie-in, area inspected approved for cover. Remaining pipe for the tie-in will be scheduled for a later date.
|