BLD18-02907
| FIRE-Final Inspection | 11/30/2018 | 11/30/2018 | 11/30/2018 2:52:55 PM | P | PASS |
|
|
Life safety passed
Tayler Phone #: ###-####
|
BLD18-02673
| FIRE-Final Inspection | 11/30/2018 | 11/30/2018 | 11/30/2018 2:24:52 PM | P | FAIL |
|
|
Need the additional address for the corner lot as discussed, need the emergency lighting corrected, need all doors and hardware installed (pocket doors to meet ADA), test the duct smoke detectors
Adam Phone #: ###-####
|
BLD17-03282
| FIRE-Final Inspection | 11/30/2018 | 11/30/2018 | 11/30/2018 2:23:26 PM | P | PASS |
|
|
Life safety passed
Adam Phone #: ###-####
|
FIR18-00590
| INSP-Sprinkler Rough-in | 11/30/2018 | 11/30/2018 | 11/30/2018 1:03:40 PM | P | PASS |
|
|
The remaining sprinkler piping is ok for cover
Contact Andrew Larson ###-#### 30 min prior to RTC Insp start...
Thought this was scheduled for AM but it didn''t save for some reason...
Thank YOU Phone #: ###-#### Inspection requested via web by Teri Cruickshank
|
FIR18-00759
| INSP-Sprinkler Rough-in | 11/30/2018 | 11/30/2018 | 11/30/2018 12:45:39 PM | P | PASS |
|
|
See the city approved plans for piping marked "ok" that is ok for cover.
Adam Phone #: ###-####
|
BLD18-03678
| FIRE-Conference | 11/29/2018 | 11/30/2018 | 11/30/2018 12:44:39 PM | A | DONE |
|
|
We went over life safety requirements.
Evan Phone #: ###-####
|
BLD18-03560
| FIRE-Conference | 11/29/2018 | 11/30/2018 | 11/30/2018 11:38:28 AM | A | DONE |
|
|
we went over life safety requirements. Need the exit signs, emergency lights, exit discharge lights as shown on the plans, need additional address numbers, need CO alarm system as per the review comments, need correct door hardware.
Tyler Phone #: ###-####
|
NAF17-00079
| INSP-Final | 11/30/2018 | 11/30/2018 | 11/30/2018 11:12:34 AM | P | PART |
|
|
A temporary for life safety is ok with Fire Dept. permission until the door hardware at the two store front doors and the pocket door for the restroom have been provided with ADA compliant hardware as per discussion. The one hour rated gas room will need to have the building inspector verify that it meets building code requirements for one hour rating and the mechanical inspector to verify mechanical code requirements.
Phone #: 2089413696 >> Inspection requested via mobile web by Bob Miffit
|
BLD18-03196
| FIRE-Final Inspection | 11/29/2018 | 11/30/2018 | 11/30/2018 10:00:32 AM | A | PART |
|
|
A temporary for life safety is being given with Ron's approval until the project related fire alarm permit is finaled. FIR18-00909
John Phone #: ###-####
|
BLD18-01585
| FIRE-Final Inspection | 11/30/2018 | 11/30/2018 | 11/30/2018 12:00:00 AM | P | CANC |
|
|
Sam Phone #: ###-####-this is residentail not commerial
|
FIR18-00896
| INSP-Sprinkler Rough-in | 11/30/2018 | 11/30/2018 | 11/30/2018 12:00:00 AM | P | CANC |
|
|
underground // Andy or Brian ###-#### Phone #: ###-####
|