Inspections for the day of: Thursday, November 4, 1999.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRick Jackson
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD99-00021 FIRE-Final Inspection11/3/199911/4/199911/4/1999 12:00:00 AMACANC
DEBEST FIRE ###-#### -PER RICK 9:00? Not ready for final
BLD99-00021 FIRE-Sprinkler Rough-in11/4/199911/4/199911/4/1999 12:00:00 AMAFAIL
Hydro test ok. Sprinkler R/I fail- not fully sprinklered (storage room); wrong heads in several areas.
BLD99-01125 FIRE-Final Inspection11/4/199911/4/199911/4/1999 12:00:00 AMAPASS
Ok for occ. signed perm. col.
BLD99-03006 FIRE-Final Inspection11/4/199911/4/199911/4/1999 12:00:00 AMPPASS
PERRY GOING OUT ALSO JAY ###-#### Occ. Approved
BLD99-02432 FIRE-Final Inspection11/4/199911/4/199911/4/1999 12:00:00 AMPNR
pat-- ###-#### fire fn Will reschedule for 11/5/99
BLD99-02443 FIRE-Final Inspection11/4/199911/4/199911/4/1999 12:00:00 AMPNR
pat--- ###-#### fire fn Will reschedule for 11/5/99
BLD99-02129 FIRE-Sprinkler Rough-in11/4/199911/4/199911/4/1999 12:00:00 AMPPASS
DON ###-#### PAGER Ok to cover 3rd floor- kitchen under separate permit.
FIR99-00404 INSP-Sprinkler Rough-in/Hydro11/4/199911/4/199911/4/1999 12:00:00 AMPPASS
JIM PAGER ###-#### Hydro ok; insulation obstructing heads in attic areas.