Inspections for the day of: Friday, November 4, 2005.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00812 INSP-Sprinkler Rough-in11/3/200511/4/200511/4/2005 4:06:42 PMPPART
2nd floor corridor hard lid and 1st floor restrooms hard lid are okay to cover for overhead rough-in.
BLD05-00922 FIRE-Final Inspection11/3/200511/4/200511/4/2005 3:49:29 PMAFAIL
See correction notice for a list of defficient items, not all items reviewed at this inspection, several issues remain.
BLD04-01324 FIRE-Final Inspection11/3/200511/4/200511/4/2005 3:46:45 PMAFAIL
Not all curb painting is completed, three exit signs and two emergency lights are not functional, exterior doors are not installed in some locations.
FIR05-00595 INSP-Final Inspection11/3/200511/4/200511/4/2005 3:43:11 PMPCANC
No inspection performed due to pending resubmittals for significant changes in actual install from approved plans per alarm plans examiner.
FIR05-00489 INSP-Final Inspection11/3/200511/4/200511/4/2005 1:19:12 PMACANC
dennis; Phone #: ###-#### Not ready for inspection per Dennis, this inspection to be scheduled for next week, was mistakenly scheduled for today.
BLD05-02877 FIRE-Final Inspection11/3/200511/4/200511/4/2005 11:44:24 AMAPART
The racking is acceptable however, the SW heads at four separate garage doors have been pushed out from under the doors and the height of the tracking raised effectively rendering the sprinklers at these locations useless, need to repair prior to rack permit approval, a separate permit may be required to perform this work.
BLD05-02908 FIRE-Final Inspection11/3/200511/4/200511/4/2005 9:50:41 AMAPASS
Life safety passed inspection, contractor to lower mounting height of the provided fire extinguisher to 48" aff to the handle as required.
BLD05-02907 FIRE-Final Inspection11/3/200511/4/200511/4/2005 9:47:52 AMAPASS
Life safety is acceptable.
BLD05-01811 FIRE-Final Inspection11/3/200511/4/200511/4/2005 9:09:11 AMACANC
rex; Phone #: ###-#### Wrong inspection request, there is no fire inspection related work associated with this permit, contacted Rex to notify him of the mistake.
FIR05-00686 INSP-Alarm Testing11/1/200511/4/200511/4/2005 8:51:56 AMAPASS
Fire alarm work passed inspection.
FIR05-00609 INSP-Final Inspection11/2/200511/4/200511/4/2005 12:00:00 AMPFAIL
Grant Ahten; Phone #: ###-#### Internet Inspection Request from: Terry Owsley

1) Need to add an additional strobe in reception area because of the column that blocks the 95 cd in the ceiling.

2) Duct detectors are installed in the return of the HP units, but the OSA is dumped into the return plenum, whereby the duct detector is actually monitoring "mixed" air.