FIR04-00812
| INSP-Sprinkler Rough-in | 11/3/2005 | 11/4/2005 | 11/4/2005 4:06:42 PM | P | PART |
|
|
2nd floor corridor hard lid and 1st floor restrooms hard lid are okay to cover for overhead rough-in.
|
BLD05-00922
| FIRE-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 3:49:29 PM | A | FAIL |
|
|
See correction notice for a list of defficient items, not all items reviewed at this inspection, several issues remain.
|
BLD04-01324
| FIRE-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 3:46:45 PM | A | FAIL |
|
|
Not all curb painting is completed, three exit signs and two emergency lights are not functional, exterior doors are not installed in some locations.
|
FIR05-00595
| INSP-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 3:43:11 PM | P | CANC |
|
|
No inspection performed due to pending resubmittals for significant changes in actual install from approved plans per alarm plans examiner.
|
FIR05-00489
| INSP-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 1:19:12 PM | A | CANC |
|
|
dennis; Phone #: ###-#### Not ready for inspection per Dennis, this inspection to be scheduled for next week, was mistakenly scheduled for today.
|
BLD05-02877
| FIRE-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 11:44:24 AM | A | PART |
|
|
The racking is acceptable however, the SW heads at four separate garage doors have been pushed out from under the doors and the height of the tracking raised effectively rendering the sprinklers at these locations useless, need to repair prior to rack permit approval, a separate permit may be required to perform this work.
|
BLD05-02908
| FIRE-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 9:50:41 AM | A | PASS |
|
|
Life safety passed inspection, contractor to lower mounting height of the provided fire extinguisher to 48" aff to the handle as required.
|
BLD05-02907
| FIRE-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 9:47:52 AM | A | PASS |
|
|
Life safety is acceptable.
|
BLD05-01811
| FIRE-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 9:09:11 AM | A | CANC |
|
|
rex; Phone #: ###-#### Wrong inspection request, there is no fire inspection related work associated with this permit, contacted Rex to notify him of the mistake.
|
FIR05-00686
| INSP-Alarm Testing | 11/1/2005 | 11/4/2005 | 11/4/2005 8:51:56 AM | A | PASS |
|
|
Fire alarm work passed inspection.
|
FIR05-00609
| INSP-Final Inspection | 11/2/2005 | 11/4/2005 | 11/4/2005 12:00:00 AM | P | FAIL |
|
|
Grant Ahten; Phone #: ###-#### Internet Inspection Request from: Terry Owsley
1) Need to add an additional strobe in reception area because of the column that blocks the 95 cd in the ceiling.
2) Duct detectors are installed in the return of the HP units, but the OSA is dumped into the return plenum, whereby the duct detector is actually monitoring "mixed" air.
|