Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00667 INSP-Final Inspection11/4/200511/4/200511/4/2005 2:34:26 PMPPASS
Permit finaled
BLD05-01900 FIRE-Final Inspection11/3/200511/4/200511/4/2005 2:30:51 PMPCANC
bob; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
FIR03-00711 INSP-Final Inspection10/28/200511/4/200511/4/2005 2:06:56 PMPPASS
permit finaled
BLD05-02938 FIRE-Final Inspection11/4/200511/4/200511/4/2005 1:49:36 PMPFAIL
mike; Phone #: ###-####
The sprinkler pendants in the entry lobby are overspaced off the north wall. This work will require a permit. Canopies are also missing in several locations. See approved plans for locations. The fire extinguishers need current inspections. Need verification of annual inspections on both the fire alarm system (duct detectors in space) and the fire sprinkler riser. Need to repair the emergency light just inside the main entry by the exit sign.
FIR03-00524 INSP-Final Inspection11/3/200511/4/200511/4/2005 1:46:52 PMAPASS
Hood suppression system operated correctly. Pull station was allowed to remain in existing position with Dave Millers permission. Extinguishers inspected as well.
FIR03-00524 INSP-Conference10/27/200511/4/200511/4/2005 12:35:02 PMPPASS
FIR05-00468 INSP-Final Inspection11/2/200511/4/200511/4/2005 12:34:17 PMAPASS
permit finaled
FIR05-00657 INSP-Final Inspection11/3/200511/4/200511/4/2005 12:26:20 PMAFAIL
Provide signage on doors as discussed. Provide longer sample tube on duct detector just inside of main doors and relocate the other duct detector closer to the roof deck and out of the 90 degree turn.
FIR05-00523 INSP-Sprinkler Rough-in/Hydro11/3/200511/4/200511/4/2005 12:25:15 PMAPASS
Anti-freeze hydro test passed.
FIR04-00004 INSP-Final Inspection11/3/200511/4/200511/4/2005 10:43:50 AMAFAIL
See review note #2 requiring verification of spacing over 148 sq.ft. This applies to the pendant heads in the two north side conference rooms.
FIR03-00424 INSP-Final Inspection11/1/200511/4/200511/4/2005 10:41:07 AMAFAIL
Need to provide outside control for the fire sprinkler riser that is associated with this upgrade. This was verified with Bill Alexander. Information was originally requested under review note C but not provided.
FIR05-00717 INSP-Final Inspection11/3/200511/4/200511/4/2005 9:26:09 AMAPASS
Hood suppression system operated correctly
FIR05-00671 INSP-Final Inspection11/3/200511/4/200511/4/2005 8:25:00 AMAPASS
Permit finaled.
FIR04-00666 INSP-Final Inspection11/3/200511/4/200511/3/2005 1:55:17 PMAPASS
Permit finaled
FIR05-00058 INSP-Final Inspection11/3/200511/4/200511/3/2005 1:54:56 PMAPASS
Permit finaled