FIR04-00667
| INSP-Final Inspection | 11/4/2005 | 11/4/2005 | 11/4/2005 2:34:26 PM | P | PASS |
|
|
Permit finaled
|
BLD05-01900
| FIRE-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 2:30:51 PM | P | CANC |
|
|
bob; Phone #: ###-#### Internet Inspection Request from: Barbara Moore
|
FIR03-00711
| INSP-Final Inspection | 10/28/2005 | 11/4/2005 | 11/4/2005 2:06:56 PM | P | PASS |
|
|
permit finaled
|
BLD05-02938
| FIRE-Final Inspection | 11/4/2005 | 11/4/2005 | 11/4/2005 1:49:36 PM | P | FAIL |
|
|
mike; Phone #: ###-#### The sprinkler pendants in the entry lobby are overspaced off the north wall. This work will require a permit. Canopies are also missing in several locations. See approved plans for locations. The fire extinguishers need current inspections. Need verification of annual inspections on both the fire alarm system (duct detectors in space) and the fire sprinkler riser. Need to repair the emergency light just inside the main entry by the exit sign.
|
FIR03-00524
| INSP-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 1:46:52 PM | A | PASS |
|
|
Hood suppression system operated correctly. Pull station was allowed to remain in existing position with Dave Millers permission. Extinguishers inspected as well.
|
FIR03-00524
| INSP-Conference | 10/27/2005 | 11/4/2005 | 11/4/2005 12:35:02 PM | P | PASS |
|
|
|
FIR05-00468
| INSP-Final Inspection | 11/2/2005 | 11/4/2005 | 11/4/2005 12:34:17 PM | A | PASS |
|
|
permit finaled
|
FIR05-00657
| INSP-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 12:26:20 PM | A | FAIL |
|
|
Provide signage on doors as discussed. Provide longer sample tube on duct detector just inside of main doors and relocate the other duct detector closer to the roof deck and out of the 90 degree turn.
|
FIR05-00523
| INSP-Sprinkler Rough-in/Hydro | 11/3/2005 | 11/4/2005 | 11/4/2005 12:25:15 PM | A | PASS |
|
|
Anti-freeze hydro test passed.
|
FIR04-00004
| INSP-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 10:43:50 AM | A | FAIL |
|
|
See review note #2 requiring verification of spacing over 148 sq.ft. This applies to the pendant heads in the two north side conference rooms.
|
FIR03-00424
| INSP-Final Inspection | 11/1/2005 | 11/4/2005 | 11/4/2005 10:41:07 AM | A | FAIL |
|
|
Need to provide outside control for the fire sprinkler riser that is associated with this upgrade. This was verified with Bill Alexander. Information was originally requested under review note C but not provided.
|
FIR05-00717
| INSP-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 9:26:09 AM | A | PASS |
|
|
Hood suppression system operated correctly
|
FIR05-00671
| INSP-Final Inspection | 11/3/2005 | 11/4/2005 | 11/4/2005 8:25:00 AM | A | PASS |
|
|
Permit finaled.
|
FIR04-00666
| INSP-Final Inspection | 11/3/2005 | 11/4/2005 | 11/3/2005 1:55:17 PM | A | PASS |
|
|
Permit finaled
|
FIR05-00058
| INSP-Final Inspection | 11/3/2005 | 11/4/2005 | 11/3/2005 1:54:56 PM | A | PASS |
|
|
Permit finaled
|