Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00647 INSP-Sprinkler Rough-in11/3/200811/4/200811/4/2008 4:25:53 PMAPART
Sprinkler rough-in is basically passed. As-builts are needed showing the pipe routing changes. Resubmittals are needed since tyco heads have been installed instead of the submitted Viking heads. Verification is needed that the cpvc underground piping is equal to or less restrictive than the submitted poly piping. A tenting inspection is needed prior to covering the piping with the blow-in insulation.
BLD08-02104 FIRE-Final Inspection11/4/200811/4/200811/4/2008 4:23:15 PMPPASS
Life safety passed
FIR08-00694 INSP-Final Inspection11/4/200811/4/200811/4/2008 4:22:00 PMPPASS
Permit finaled
FIR07-00874 INSP-Sprinkler Rough-in11/3/200811/4/200811/4/2008 1:39:47 PMAPART
The above ground hydro test for the new dining room passed and the piping can be covered.
BLD08-02301 FIRE-Final Inspection11/3/200811/4/200811/4/2008 12:07:37 PMAPART
A temporary occupancy was given until automatic flush bolts are provided for the inactive leaf on the main exit.