FIR09-00540
| INSP-Sprinkler Rough-in | 11/4/2009 | 11/4/2009 | 11/4/2009 3:32:14 PM | P | NH |
|
|
|
FIR09-00384
| INSP-Sprinkler Rough-in | 11/4/2009 | 11/4/2009 | 11/4/2009 3:27:39 PM | P | PART |
|
|
Okay to cover except the SW area where combustible construction above the drop ceilings is exposed, noted one upright head to be relocated due to obstruction by a truss web at the attic area north side, insulation at two branchline feeds to dry sidewall heads adjusted while on site, remainder of previously noted correction items are finished, minor field modifications at some locations okayed, still need to verify insulation install at exterior canopies as discussed.
|
FIR09-00501
| INSP-Sprinkler Rough-in | 11/4/2009 | 11/4/2009 | 11/4/2009 3:20:59 PM | P | PART |
|
|
Inspection at overhead upright protection completed okay with the exception of one head (incorrect type) to be replaced and an unprotected pocket at the west side of the tenant space to be filled with non-combustible insulation to meet the allowed exception or provided with sprinklers as discussed.
|
BLD09-01689
| FIRE-Final Inspection | 11/4/2009 | 11/4/2009 | 11/4/2009 3:16:01 PM | P | NR |
|
|
Construction underway, work in progress.
|
FIR09-00627
| INSP-Sprinkler Rough-in | 11/4/2009 | 11/4/2009 | 11/4/2009 3:15:10 PM | P | PART |
|
|
Overhead fire sprinkler installation is approved for cover, service line and backflow prevention device are not yet complete.
|
FIR09-00527
| INSP-Final Inspection | 10/29/2009 | 11/4/2009 | 11/4/2009 3:13:15 PM | A | PASS |
|
|
Fire alarm permit work okayed for final status, inspection passed.
|
FIR09-00526
| INSP-Final Inspection | 10/29/2009 | 11/4/2009 | 11/4/2009 3:12:39 PM | A | PASS |
|
|
Fire alarm passed site testing, permit final approved.
|
FIR09-00564
| INSP-Final Inspection | 10/29/2009 | 11/4/2009 | 11/4/2009 3:12:06 PM | A | PASS |
|
|
Fire alarm work passed field testing, permit finaled.
|
FIR09-00536
| INSP-Conference | 11/4/2009 | 11/4/2009 | 11/4/2009 3:11:34 PM | A | DONE |
|
|
Regarding sprinkler coverage at the main entry exterior canopy.
|
BLD09-00616
| FIRE-Conference | 11/4/2009 | 11/4/2009 | 11/4/2009 11:43:51 AM | P | DONE |
|
|
Some issues noted during the project related fire sprinkler cover inspection include: missing electrical supervision of the main control valve for the existing riser-see fire code review note #21, also verify system is current with an annual certification-see note #17, complete protection for the basement per NFPA 13 shall be provided-see note #13- per NFPA 13 2007 sec. 8.6.7.1 sprinklers shall be required in all ceiling pockets unless exceptions 1-7 are met per 8.6.7.2 including item (2) depth of the unprotected pocket does not exceed 36" and item (7) quick response sprinklers are provided throughout the compartment. See also project related fire alarm permit FIR09-00418 review comments items #19, and 6,7, 12 regarding locations of smoke and heat detectors, in particular item #11 referencing NFPA 72 2007 sec. 6.16.4.2 stating heat detectors used for elevator power shut down shall be placed within 2ft of each sprinkler head and be installed per requirements of Chapter 5.
|