Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR10-00326 INSP-Final Inspection11/4/201011/4/201011/5/2010 2:22:26 PMAPASS
Permit finaled
BLD10-02521 FIRE-Final Inspection11/2/201011/4/201011/4/2010 3:49:44 PMPFAIL
Provide emergency lighting for both the office and the warehouse areas. Provide additional exit door in warehouse. Provide verification on which doors are required to swing out. Remove all locking hatches and thumbturns. Provide automatic flush bolts on both main doors. Provide single action hardware on door from entrance office. Verify/provide at least a total of 13 (qty) "4A" classification fire extingguishers in the warehouse. Finish/final the project related fire alarm and fire sprinkler permits. Resubmit plans for review of high pile storage requirements of IFC chapter 23. Ryan Phone #: ###-####
FIR10-00400 INSP-Final Inspection11/3/201011/4/201011/4/2010 3:40:31 PMPFAIL
Todays inspection was actually just an underground flush which passed inspection. This project is not ready for a final inspection at this time. See previous correction items noted.
FIR10-00468 INSP-Final Inspection11/3/201011/4/201011/4/2010 12:21:11 PMAPASS
Permit finaled
BLD10-01267 FIRE-Final Inspection11/3/201011/4/201011/4/2010 10:07:19 AMAPASS
life safety passed.
FIR10-00238 INSP-Final Inspection11/4/201011/4/201011/4/2010 10:04:28 AMPPASS
Permit finaled
BLD10-02462 FIRE-Final Inspection11/3/201011/4/201011/4/2010 9:50:42 AMAFAIL
Remove all locking hardware from the common restroom corridor as stated in red on the city approved drawings. These locks are to be removed permenantly
BLD10-02468 FIRE-Final Inspection11/3/201011/4/201011/4/2010 9:08:33 AMAFAIL
Replace the painted sprinkler head in the restroom, provide non locking hardware on the door below the exit sign, provide annual inspection for the fire extinguisher, provide verification of the annual inspection for the fire sprinkler system, provide single action hardware for the rear exit door and remove the manual deadbolt.