Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00602 INSP-Final Inspection11/4/201311/4/201311/4/2013 3:47:53 PMPPASS
Permit finaled
FIR13-00342 INSP-Supply line flush11/1/201311/4/201311/4/2013 3:25:07 PMPCANC
Rescheduled for tomorrow morning.
BLD13-01319 FIRE-Final Inspection11/1/201311/4/201311/4/2013 3:24:20 PMPCANC
Waiting for the project related fire alarm and fire sprinkler permits to be addressed first.
FIR13-00363 INSP-Final Inspection11/4/201311/4/201311/4/2013 3:20:55 PMPPASS
permit finaled
FIR13-00584 INSP-Final Inspection11/4/201311/4/201311/4/2013 3:20:11 PMPFAIL
Need as-built drawings showing the interconnection of the door mags into the facp and functional testing. All other items passed.
FIR13-00571 INSP-Sprinkler Rough-in11/1/201311/4/201311/4/2013 3:17:35 PMPCANC
Per Anthony work is not done yet. Rescheduled for tomorrow Phone #: ###-####
FIR13-00379 INSP-Final Inspection11/4/201311/4/201311/4/2013 2:55:02 PMPPASS
Permit finaled
FIR13-00362 INSP-Final Inspection11/4/201311/4/201311/4/2013 2:54:13 PMPPASS
Permit finaled
BLD13-00440 FIRE-Final Inspection11/4/201311/4/201311/4/2013 2:52:20 PMPPART
A temporary occupancy is given with Scott Arellano's permission for a max of 10 days. Items needing correct are the fire doors do not have activation per NFPA 80 (links on both sides), access controled egress doors do not have sensors or connection to the fire alarm system per IFC 1008.1.4.4, exit discharge lights need to be installed, add exit sign/emergency light in corridor, install tile in office, contact fire dept for gate at west side of building that is only 14'-6" wide.
FIR13-00343 INSP-Final Inspection11/1/201311/4/201311/4/2013 10:51:22 AMPCANC
James Raff is the contact. Thanks Phone #: ###-#### >> Inspection requested via web by Stan Beus Inspection cancelled from web by: Stan Beus
FIR13-00602 INSP-Sprinkler Rough-in11/1/201311/4/201311/4/2013 10:34:10 AMAPASS
Rough-in passed
BLD13-01606 FIRE-Final Inspection11/4/201311/4/201311/4/2013 10:33:41 AMPPASS
life safety passed
BLD13-01681 FIRE-Final Inspection11/1/201311/4/201311/4/2013 10:33:11 AMAPASS
Life safety passed