Inspections for the day of: Monday, November 4, 2013.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorDaryl DeGrange
TitleELE-INSPECTION SUPV
Phone #794-1379
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-03045 Final11/4/201311/4/201311/4/2013 3:01:56 PMPPASS
Please call prior to arrival... Thank you! Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld GFCI protection not required for this type of equipment, job complete, final ok
ELE13-03033 Rough-In Permanent Service11/4/201311/4/201311/4/2013 2:05:07 PMPFAIL
Phone #: ###-#### >> Inspection requested via web by daniel bibikov BCC Unlawful to conceal electrical wiring until inspection has been performed. Weatherization has also been performed before inspection NEC 324.23 Guard strips required for all cables crossing over trusses within 6 ft. of attic access. NEC 334.30 Shall staple NM cable within fixture box. Hall fixture top of stairs
ELE13-02614 Electrical Rough-In11/4/201311/4/201311/4/2013 12:43:11 PMPPASS
Contact: Tom Hartung. underground inspection please. early afternoon if possible Phone #: ###-#### >> Inspection requested via web by Deb Gooden Rough-in ok cover underground service feeder conduits and concrete encased electrode
ELE13-03064 Electrical Rough-In11/4/201311/4/201311/4/2013 12:13:53 PMPPASS
Mike Phone #: ###-#### rough-in ok
ELE13-01811 Rough-In Permanent Service11/4/201311/4/201311/4/2013 10:20:48 AMPFAIL
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe NEC 310.15 Table 310.16 Service part of inspection failed due to over current device to high for #2 SER ampacity
ELE13-01811 Electrical Rough-In11/4/201311/4/201311/4/2013 10:12:43 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe Rough-in ok cover garage and upstairs addition, but not that area of master bathroom expansion.
ELE13-03065 Rough-In Permanent Service11/3/201311/4/201311/4/2013 9:21:53 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey NEC 320.23 Guard strips for NM cables going across truss within 6 ft. of attic access NEC 210.52(1) Need receptacle on small appliance circuit right of dinning room slider door.
ELE13-03060 Electrical Rough-In11/3/201311/4/201311/4/2013 8:56:06 AMAPASS
underground conduits in sales area
Phone #: ###-#### >> Inspection requested via web by Stan Woodward rough-in ok cover underground (under concrete)
ELE12-02735 Electrical Rough-In11/1/201311/4/201311/4/2013 8:38:25 AMAPASS
Bud on site. Wall rough-in for Phase 2B South Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover walls
ELE13-03063 Temporary Service11/1/201311/4/201311/4/2013 8:17:51 AMAFAIL
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson GFCI receptacles are both broken
ELE13-03062 Temporary Service11/1/201311/4/201311/4/2013 8:16:41 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson t/s u/g n ok