ELE13-03045
| Final | 11/4/2013 | 11/4/2013 | 11/4/2013 3:01:56 PM | P | PASS |
|
|
Please call prior to arrival... Thank you! Phone #: ###-#### >> Inspection requested via web by Daniel Schaffeld GFCI protection not required for this type of equipment, job complete, final ok
|
ELE13-03033
| Rough-In Permanent Service | 11/4/2013 | 11/4/2013 | 11/4/2013 2:05:07 PM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by daniel bibikov BCC Unlawful to conceal electrical wiring until inspection has been performed. Weatherization has also been performed before inspection NEC 324.23 Guard strips required for all cables crossing over trusses within 6 ft. of attic access. NEC 334.30 Shall staple NM cable within fixture box. Hall fixture top of stairs
|
ELE13-02614
| Electrical Rough-In | 11/4/2013 | 11/4/2013 | 11/4/2013 12:43:11 PM | P | PASS |
|
|
Contact: Tom Hartung. underground inspection please. early afternoon if possible Phone #: ###-#### >> Inspection requested via web by Deb Gooden Rough-in ok cover underground service feeder conduits and concrete encased electrode
|
ELE13-03064
| Electrical Rough-In | 11/4/2013 | 11/4/2013 | 11/4/2013 12:13:53 PM | P | PASS |
|
|
Mike Phone #: ###-#### rough-in ok
|
ELE13-01811
| Rough-In Permanent Service | 11/4/2013 | 11/4/2013 | 11/4/2013 10:20:48 AM | P | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe NEC 310.15 Table 310.16 Service part of inspection failed due to over current device to high for #2 SER ampacity
|
ELE13-01811
| Electrical Rough-In | 11/4/2013 | 11/4/2013 | 11/4/2013 10:12:43 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Rowdy Monroe Rough-in ok cover garage and upstairs addition, but not that area of master bathroom expansion.
|
ELE13-03065
| Rough-In Permanent Service | 11/3/2013 | 11/4/2013 | 11/4/2013 9:21:53 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Neal Rumsey NEC 320.23 Guard strips for NM cables going across truss within 6 ft. of attic access NEC 210.52(1) Need receptacle on small appliance circuit right of dinning room slider door.
|
ELE13-03060
| Electrical Rough-In | 11/3/2013 | 11/4/2013 | 11/4/2013 8:56:06 AM | A | PASS |
|
|
underground conduits in sales area Phone #: ###-#### >> Inspection requested via web by Stan Woodward rough-in ok cover underground (under concrete)
|
ELE12-02735
| Electrical Rough-In | 11/1/2013 | 11/4/2013 | 11/4/2013 8:38:25 AM | A | PASS |
|
|
Bud on site. Wall rough-in for Phase 2B South Phone #: ###-#### >> Inspection requested via web by Clint Tate rough-in ok cover walls
|
ELE13-03063
| Temporary Service | 11/1/2013 | 11/4/2013 | 11/4/2013 8:17:51 AM | A | FAIL |
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson GFCI receptacles are both broken
|
ELE13-03062
| Temporary Service | 11/1/2013 | 11/4/2013 | 11/4/2013 8:16:41 AM | A | PASS |
|
|
Phone #: ###-#### >> Inspection requested via web by Therrin Robertson t/s u/g n ok
|