FIR14-00542
| INSP-Sprinkler Rough-in | 11/4/2014 | 11/4/2014 | 11/5/2014 3:49:52 PM | P | PART |
|
|
UG supply line
|
FIR14-00527
| INSP-Final Inspection | 11/4/2014 | 11/4/2014 | 11/4/2014 3:55:34 PM | P | PASS |
|
|
Final walkthrough completed. Fire sprinkler permit finaled.
|
FIR14-00782
| INSP-Sprinkler Rough-in | 11/4/2014 | 11/4/2014 | 11/4/2014 3:54:42 PM | P | PART |
|
|
Okayed for cover at the elevator lobby sheetrock ceiling.
|
BLD14-01249
| FIRE-Final Inspection | 11/3/2014 | 11/4/2014 | 11/4/2014 2:27:13 PM | A | PASS |
|
|
Site inspection passed.
|
FIR14-00344
| INSP-Sprinkler Rough-in | 11/3/2014 | 11/4/2014 | 11/4/2014 11:59:20 AM | A | PART |
|
|
Completed rough-in for install to date at the first floor wet system building areas A, B, and C. Refer to dated annotations on plan sheet for locations and items noted including; missing coverage at HVAC closet unit B105, relocate head at unit B106 kitchen, revise hangers at end of pendent armovers various locations, as-builts needed for field modifications such as relocated 2" main, moved SW, deleted SW coverage at area A, branchline re-routes, etc., corridor main is not yet installed, 3 groups of rooms as clouded NR.
|
BLD14-02919
| FIRE-Final Inspection | 11/3/2014 | 11/4/2014 | 11/4/2014 11:51:58 AM | A | FAIL |
|
|
Missing exit sign per approved plan, delayed egress function at new door is not reflected on drawings or provided with conditions to be met per IFC 2012 1008.1.9.7.
|
BLD14-03096
| FIRE-Final Inspection | 11/3/2014 | 11/4/2014 | 11/4/2014 11:51:33 AM | A | FAIL |
|
|
Missing exit sign per approved plan, delayed egress function at new door is not reflected on drawings or provided with conditions to be met per IFC 2012 1008.1.9.7.
|
FIR14-00515
| INSP-Final Inspection | 11/2/2014 | 11/4/2014 | 11/4/2014 9:40:51 AM | A | PASS |
|
|
Fire alarm work passed functional testing and site inspection. Permit finaled.
|