FIR08-00460
| INSP-Final Inspection | 11/4/2008 | 11/5/2008 | 11/5/2008 4:43:34 PM | P | FAIL |
|
|
Noted two non-functional notification devices-locations marked on plans, hall 417 is missing adequate coverage, wall mounted a/v's at all perimeter open office locations are mounted below min. height AFF per NFPA 72, added area SD at the common corridors to be indicated on resubmitted plans. See also review note comments 10 and 11.
|
FIR08-00364
| INSP-Final Inspection | 11/5/2008 | 11/5/2008 | 11/5/2008 4:20:23 PM | P | PASS |
|
|
Remainder of fire alarm testing completed satisfactory, fire alarm permit finaled.
|
FIR07-01042
| INSP-Sprinkler Rough-in | 11/5/2008 | 11/5/2008 | 11/5/2008 4:15:46 PM | P | PART |
|
|
Remote FDC UG piping okayed for cover per resubmittals.
|
FIR08-00332
| INSP-Final Inspection | 10/31/2008 | 11/5/2008 | 11/5/2008 4:13:43 PM | A | DEFR |
|
|
Phone #: ###-#### Internet Inspection Request from: Wayne Berry
|
BLD08-01775
| FIRE-Final Inspection | 11/4/2008 | 11/5/2008 | 11/5/2008 4:13:24 PM | A | PASS |
|
|
Fire life safety inspection passed, one EM light repaired while on site, missing doors to be verified for compliant hardware at structural final.
|
FIR08-00018
| INSP-Sprinkler Rough-in/Hydro | 11/4/2008 | 11/5/2008 | 11/5/2008 11:29:18 AM | A | FAIL |
|
|
Inspection for overhead cover at the 1st level parking garage exit failed due to a soffit obstruction, circled location on plans. The two adjacent branchlines to the north are okay for cover.
|
FIR08-00489
| INSP-Final Inspection | 11/5/2008 | 11/5/2008 | 11/5/2008 11:09:25 AM | P | PASS |
|
|
Demo permit work finished, permit finaled.
|
BLD08-02330
| FIRE-Final Inspection | 11/5/2008 | 11/5/2008 | 11/5/2008 10:56:39 AM | A | PASS |
|
|
C/N items repaired, fire life safety passed.
|
FIR08-00239
| INSP-Sprinkler Rough-in/Hydro | 11/4/2008 | 11/5/2008 | 11/5/2008 10:42:47 AM | A | PART |
|
|
Inspection to verify non-sprinklered concealed attic pockets at the 2nd floor east side are entireley filled with non-combustible insulation to meet exception requirements per NFPA 13 as discussed.
|
FIR08-00479
| FIR-Aging Inspection | 11/5/2008 | 11/5/2008 | 11/5/2008 10:29:08 AM | | DONE |
|
|
Pending site inspection request.
|
FIR08-00489
| FIR-Aging Inspection | 11/5/2008 | 11/5/2008 | 11/5/2008 10:26:47 AM | | DONE |
|
|
Scope of work has been completed, okay to final.
|
BLD08-01595
| FIRE-Final Inspection | 11/4/2008 | 11/5/2008 | 11/5/2008 12:00:00 AM | A | CANC |
|
|
vaugn Note: North face TI Phone #: ###-####
|