Inspections for the day of: Wednesday, November 5, 2014.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00179 ELE-Aging Inspection11/5/201411/5/201411/5/2014 3:56:19 PM DONE
Still under constrution
ELE10-01304 ELE-Aging Inspection11/5/201411/5/201411/5/2014 3:53:51 PM DONE
Still under construction
ELE14-02902 Final11/5/201411/5/201411/5/2014 3:51:18 PMPFAIL
If you have any questions, please call Zack ###-####, thank you. Phone #: ###-#### Inspection requested via web by Clay Morgan Devices not installed, hot tub wiring not complete
ELE14-02902 Electrical Rough-In11/5/201411/5/201411/5/2014 3:43:42 PMPPASS
If you have any questions, please call Zack ###-####, thank You. Phone #: ###-#### Inspection requested via web by Clay Morgan Garage rough in ok cover
ELE14-03059 Conference11/5/201411/5/201411/5/2014 3:18:08 PMPDONE
Conference requested with Daryl DeGrange. Please contact Jim Snodgrass so he can meet inspector on site. Phone #: ###-#### Inspection requested via web by Todd Sellman Found building 1 service ungrounded from original install. will drive 2 ground rods and bond metal water piping system on exterior underground 30' to south in planter due to interior piping not accessible.
ELE14-03090 Electrical Rough-In11/4/201411/5/201411/5/2014 2:25:29 PMPPART
Phone #: ###-#### Inspection requested via web by Aaron Decker 250.140 Circuit for double oven shall have seperate grounding and grounded conductors. OK foam seal only
ELE14-02878 Final11/5/201411/5/201411/5/2014 1:58:00 PMPFAIL
Garage code 0500 Phone #: ###-#### Inspection requested via web by daniel bibikov Circuit feeding garage dead. Unable to inspect.
ELE14-03028 Rough-In Permanent Service11/5/201411/5/201411/5/2014 1:26:52 PMPPASS
Phone #: ###-#### Inspection requested via web by daniel bibikov Rough in ok cover p/s u/g n ok
ELE14-02870 Electrical Rough-In11/5/201411/5/201411/5/2014 1:02:06 PMPPASS
ready for a ceiling inspection for cover thanks Phone #: ###-#### Inspection requested via web by Don Lustig Ceiling grid rough in ok cover
ELE14-00212 Conference11/5/201411/5/201411/5/2014 12:43:21 PMPFAIL
BCC 4-05-32- Code violations not to be retained.
NEC 322.56- Splices where made shall be in listed junction boxes.
NEC 394.12(5)- Concealed knob-and-tube wiring. Uses not permitted. (5) Hollow spaces of walls, ceilings, and attics where such spaces are insulated by loose, rolled, or foamed in place insulating material that envelops conductors.
* During kitchen repair open splices and concealed knob-and-tube wiring found buried in insulation in walls and ceilings. Due to fire hazard this wiring shall be replaced.
ELE14-03071 Permanent Service11/4/201411/5/201411/5/2014 10:33:12 AMAPASS
The service is ready for inspection, please look at the existing panel on the stairway as we are wanting to leave it and leaving the circuits that will be powering the existing areas, all new areas will have new circuits from the exterior new panel, any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Due to interior existing walls not being opened up panel location to remain and continue to feed existing portion of house. p/s u/g n ok
ELE14-02837 Final11/4/201411/5/201411/5/2014 10:14:50 AMAFAIL
Any questions please let me know, thx, TW. Phone #: ###-#### Inspection requested via web by Stephen Kren Power feeding garage from new service which is not energized yet. Recall when able to test recepticals.
ELE14-02380 Final11/4/201411/5/201411/5/2014 9:51:16 AMAPASS
Phone #: ###-#### Inspection requested via web by Laurie Hoelscher UL listing and disconnecting means confirmed. Final ok
ELE14-03089 Electrical Rough-In11/5/201411/5/201411/5/2014 9:23:43 AMAPASS
cover for furnace room. Light box, switch and outlet box. Phone #: ###-#### Inspection requested via web by John Edwards Open homeowners permit ele14-02136 as well. Area noted rough in ok cover
ELE14-02213 Electrical Rough-In11/4/201411/5/201411/5/2014 8:58:36 AMAPART
Mike Phone #: ###-#### Upper parapet wall rough in ok cover
ELE14-02937 Electrical Rough-In11/2/201411/5/201411/2/2014 2:46:57 PMACANC
Phone #: 2088671666 >> Inspection requested via mobile web by Melinda Inspection cancelled via mobile web on Sunday, November 02, 2014.